24VNA6: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
16
If the outdoor air or coil thermistor should fail, the control will flash the
appropriate fault code (see Table 7.)  
IMPORTANT: The outdoor air thermistor and coil thermistor should be
factory mounted in the final locations.  Check to ensure thermistors are
mounted properly (See Fig. 28, Fig. 29 and Fig. 30).
Outdoor Air Thermistor
The outdoor air thermistor is a 10Kohm resistor used for multiple system
operations.    It  provides  the  outdoor  air  temperature  to  the  primary
control  module  and  user  interface.    It  is  essential  for  controlling  the
system  and  is  used  in  almost  all  modes  of  operation.    The  sensor  is
mounted in the control box per Fig. 28.
A200045
Fig. 28 – Outdoor Air Thermistor Mounting Location
Outdoor Coil Thermistor
The  outdoor  coil  thermistor  is  a  10Kohm  resistor  used  for  multiple
system  operations.    It  provides  the  coil/liquid  line  temperature  to  the
primary control module and user interface.   It is used for low ambient
operation  and  assistance  with  OAT  temperature  measurement.    The
sensor  must  be  securely  mounted  to  the  tube  connecting  the  coil  and
distributor.   See  Fig. 29  for  proper  placement.   See  Table 4  for  proper
resistances.
A200046
Fig. 29 – Outdoor Coil Thermistor Mounted on Coil
Discharge Thermistor (ODT)
Discharge thermistor is used for protection against over temperature of
the  compressor  and  the  discharge  superheat  calculations.    Proper
mounting is required to ensure that the unit exits the start-up mode.  The
ODT is located on the compressor discharge stub-out (see Fig. 30).
A200086
Fig. 30 – Discharge Thermistor (ODT) Mounting Locations
Failed Thermistor Default Operation
Factory defaults have been provided in the event of failure of outdoor air
thermistor (OAT) and/or outdoor coil thermistor (OCT). 
If  the  OAT  sensor  should  fail  the  outdoor  unit  will  operate  at  a  fixed
speed. 
If  the OCT sensor  should fail,  the  outdoor unit  will  operate  at  a fixed
speed. 
Variable Speed Compressor Winding Resistance
This  compressor  operates  with  3-phase  variable  frequency  PWM
variable  voltage.  For  troubleshooting  certain  fault  codes    related  to
compressor resistances, follow these steps:
1. Disconnect compressor power leads from the inverter terminals, 
U (YEL), V (RED), and W (BLK).
2. Measure  the  resistance  between YEL  to  RED, YEL  to  BLK,  and
RED  to  BLK  and  compare  to  Table 6 values. Each  resistance  set
should be equal.
3. Measure the resistance to ground for each lead.
4. If  the  resistances  are  correct  then  reconnect  power  leads  to
appropriate terminal.
5. If  the  resistances  appear  to  be  abnormal,  it  will  be  necessary  to
measure the resistance at the compressor fusite terminals.
6. Remove  the  sound  blanket  and  harness  plug,  measure  the
resistances, and compare to Table 6.
7. Reinstall  compressor  sound  blanket  making  sure  discharge
thermistor and compressor power harness are routed as they were
from the factory
Table 5 – ODT Resistance Values versus Temperatures
TEMPERATURE (°C) RESISTANCE (K OHMS)
25 50.15 + / - 5.0%
75 7.565 + / - 3.0%
125 1.7  + / - 1.4%
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage and/or
improper operation.
In order to minimize the ambient influence, make sure  the  thermistor
curved surface hugs the pipe surface and is secured tight using the wire
tie fished through the original slot, insulating polymer body.
Table 6 – Variable Speed Compressor Resistances
(winding resistance at 68°F? (20°F)
WINDING 24 36 48 60
Between terminals T1, T2, and T3 .74 .453 .424 .424
Between terminal & ground >1 mega OHM