24VNA6: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
Final Tubing Check
IMPORTANT:  Check to be certain  factory tubing  on both indoor and
outdoor  unit  has  not  shifted  during  shipment.  Ensure  tubes  are  not
rubbing  against  each  other  or  any  sheet  metal.  Pay  close  attention  to
feeder tubes, making sure wire ties on feeder tubes are secure and tight.  
Step 8 – Make Electrical Connections
Be  sure  field  wiring  complies with  local  and national  fire,  safety,  and
electrical codes, and  voltage  to  system  is within limits  shown  on  unit
rating  plate.  Contact  local  power  company  for  correction  of  improper
voltage. See unit rating plate for recommended circuit protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and
could affect unit reliability. See unit rating plate.  Do not install unit in
system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE:  Install  branch  circuit  disconnect  of  adequate  size  per  NEC  to
handle  unit  starting  current.  Locate  disconnect  within  sight  from  and
readily accessible from unit, per Section 440-14 of NEC.
Route Ground and Power Wires
Remove access panel to gain  access to unit wiring. Extend wires from
disconnect  through  power  wiring  hole  provided  and  into  unit  control
box.
Connect Ground and Power Wires
Connect  ground  wire  to  ground  connection  in  control  box  for  safety.
Connect power wiring to contactor as shown in Fig. 9.
A14028
Fig. 9 – Line Power Connections
Connect Control Wiring
Connect  to  Infinity  connections.    Only  two  wires  (AB)  to  Infinity
capable  indoor  unit  (furnace  or  fan  coil)  is  required.    Typical  4  wire
(ABCD) may be connected (see Fig. 5) 
IMPORTANT:  This  system  requires  the  power  supply  to  the  outdoor
unit, and  the  indoor unit,  for  the  UI  to  communicate  with the  outdoor
unit.
General Information
Use No. 18 AWG or larger color-coded, insulated (35°C minimum) wire
for low voltage control wires.
All wiring must be NEC Class 2 and must be separated from incoming
power leads. 
Use furnace transformer, fan coil transformer, or accessory transformer
for control power requirement of system accessories external to the OD
unit. The outdoor unit has its own transformer power.
Installations  using  greater  than  200  feet  of  low voltage  wiring  should
consult  the  Infinity  wall  control  manual  for  additional  guidelines
regarding  daisy  chaining  wiring  method  and  terminating  resistors.
Never route control wiring in parallel to high voltage power wires when
possible  as  electrical  noise  may  transfer  and  generate  nuisance  fault
codes.    Where  low  voltage  control  and  high  voltage  wires  must  cross
paths, do so at perpendicular angles to eliminate transferred noise.  
If  further  communication  issues  exist,  consider  using  shielded  low
voltage  wires  and  only  connect  shielding  to  C  terminal  at  end  nearest
indoor coil.  
Final Wiring Check
IMPORTANT:  Check  factory  wiring  and  field  wire  connections  to
ensure terminations are secured properly. Check wire routing to ensure
wires are not in contact with tubing, sheet metal, etc.
Step 9 – Compressor Crankcase Heater
This compressor has a standard crankcase heater.  Furnish power to the
unit a minimum of 24 hr before starting the unit for the first time. 
To  furnish  power  to  heater  only,  set  thermostat  to  OFF  and  close
electrical disconnect to outdoor unit.  
Power  is  not  required  to  the  indoor  unit  or  User  Interface  for  proper
operation  of  heater.    Crankcase  heater  will  however  be  intelligently
energized as needed even when the UI and indoor unit is not installed, as
long as there is power to the outdoor unit even if the indoor unit and UI
are not yet installed. 
Airflow Setup for Infinity Control Furnace or FE 
Fan Coil (communicating)
This  system  can  only  be  installed  with  Infinity-capable  indoor  and
Infinity  System  Control  .  When  using  an  Infinity  control,  airflow  is
automatically selected based on equipment size.  The user has the option
of  selecting  Comfort,  Efficiency  and  Max  airflow  for  Cooling  modes.
These  should  be  selected  based  on  balance  between  the  homeowner’s
comfort  and  energy  consumption  expectations.  See  User  Interface
Installation Instructions for additional available adjustments. 
NOTE:  Ensure  control  is  updated  with  the  latest  available  software
version.
Due to using a communicating control with the fan coil or the furnace,
dip  switch  adjustments  are  not  necessary.    The  outdoor  unit
configuration and the indoor airflows are determined by communicating
control setup.
Verify that the PCM, VFD and wall control are the latest software before
proceeding with the next steps.
Step 10 – Install Accessories
There  are  no  refrigeration  circuit  or  electrical  accessories  required  or
available for installation within the unit.  External to the unit, the same
accessories  such  as  the  liquid  line  solenoid,  support  feet,  snow  rack,
wind baffle etc., are available on other Carrier units can also be used on
this  line  of  product.    Refer  to  the  individual  Installation  Instructions
packaged with kits or accessories when installing.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do  not  supply  power  to  unit  with  compressor  terminal  box  cover
removed.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The  unit  cabinet  must  have  an  uninterrupted  or  unbroken  ground  to
minimize personal injury if an electrical fault should occur. The ground
may  consist  of  electrical  wire  or  metal  conduit  when  installed  in
accordance with existing electrical codes.
DISCONNECT
PER N. E. C. AND/OR
LOCAL CODES
TERMINAL
BLOCK
GROUND
LUG
FIELD GROUND
WIRING
FIELD POWER
WIRING