24VNA6: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
6
Outdoor Unit Connected to Factory-Approved Indoor 
Unit
Outdoor  unit  contains  correct  system  refrigerant  charge  for  operation
with  factory-approved,  AHRI-rated  smallest  indoor  unit      when
connected  by  15  ft.  (4.57  m)  of  field-supplied  or  factory-accessory
tubing,  and  factory-supplied  filter  drier.  Check  refrigerant  charge  for
maximum efficiency.
NOTE: If the indoor furnace coil width is more than the furnace casing
width,  refer  to  the  indoor  coil  Installation  Instructions  for  transition
requirements.
Install Liquid-Line Filter Drier Indoor
Refer to Fig. 6 and install filter drier as follows on 24, 36 and 48 size
models:
1. Braze 5-in. (127 mm) liquid tube to the indoor coil. 
2. Wrap filter drier with damp cloth. 
3. Braze filter drier to above 5-in. (127 mm) liquid tube. 
4. Connect and braze liquid refrigerant tube to the filter drier.
Refer to Fig. 7 and install filter drier as follows on 60 size models:
1. After wrapping the liquid service valve with a wet cloth braze 5-in.
(127 mm) liquid tube to the liquid service valve on outdoor unit. 
2. Wrap filter drier with damp cloth. 
3. Braze filter drier to above 5-in. (127 mm) liquid tube. 
4. Connect and braze liquid refrigerant tube to the filter drier.
A05178
Fig. 6 – Liquid-Line Filter Drier for 2, 3 & 4 Ton Applications
A200059
Fig. 7 – Liquid-Line Filter Drier for 5 Ton Applications
Refrigerant Tubing connection Outdoor
Connect vapor tube to fitting on outdoor unit vapor service valves (see
Table 1).  
Sweat Connections
Use refrigerant grade tubing. Service valves are closed from factory and
ready for brazing. After wrapping service valve with a wet cloth, braze
sweat  connections  using  industry  accepted  methods  and  materials.
Consult local code requirements. Refrigerant tubing and indoor coil are
now  ready  for  leak  testing.  This  check  should  include  all  field  and
factory joints.
Evacuate Refrigerant Tubing and Indoor Coil
Refrigerant  tubes  and  indoor  coil  should  be  evacuated  using  the
recommended deep vacuum method of 500 microns. The alternate triple
evacuation  method  may  be  used.    See  Service  Manual  for  triple
evacuation method. Always break a  vacuum with  dry  nitrogen prior to
opening the refrigerant system for servicing.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a
vacuum  of  500  microns  and  a  vacuum  gauge  capable  of  accurately
measuring  this  vacuum  depth.  The  deep  vacuum  method  is  the  most
positive  way  of assuring a  system is  free of  air and  liquid water.  (See
Fig. 8)
A95424
Fig. 8 – Deep Vacuum Graph
CAUTION
!
UNIT DAMAGE HAZARD
Failure  to follow  this  caution  may  result  in  unit  damage  or  improper
operation.
Installation of filter drier in liquid line is required.
EXTERIOR
WALL
LIQUID LINE
FILTER DRIER
TO DWELLING
CAUTION
!
UNIT DAMAGE HAZARD
Failure  to  follow  this  caution  may  result  in  equipment  damage  or
improper operation.
• Use a brazing shield
• Wrap service valves with wet cloth or heat sink material.
CAUTION
!
UNIT DAMAGE HAZARD
Failure  to  follow  this  caution  may  result  in  equipment  damage  or
improper operation.
Never use the system compressor as a vacuum pump.
500
MINUTES
01234567
1000
1500
LEAK IN
SYSTEM
VACUUM TIGH
TOO WET
TIGHT
DRY SYSTEM
2000
MICRONS
2500
3000
3500
4000
4500
5000