– 104 –
8-5-2. Operation from the indoor remote controller is not accepted, and a check code is
displayed on the 7-segment display of the interface PC board of the header unit.
8-5-3. There is no display of a check code on the 7-segment display on the interface PC board
of the header unit, although there is indoor unit that is not accepting operation from the
indoor remote controller.
Indoor remote 
controller 
status
Header unit 
7-segment 
display
Cause Countermeasures
No response
L08
Line addresses and indoor addresses of all the connected 
indoor units are not set.
Set up addresses.
There is no header unit of group control. Set up a group address.
E19 ⇔ -00
Alternate 
blinking
Indoor unit power is not turned on. Turn on the power again. (In the order: 
indoor → outdoor)
Indoor/outdoor communication line is not correctly connected 
to the U1/U2 terminal of the header unit ( Fig. 1). (Indoor/
outdoor cannot communicate before address setup.)
Correct wiring
There is no of outdoor terminal resistance, or there 
are two or more resistances (before address setup).
Check SW30 bit 2 of the header unit.
No connection between multiple refrigerant 
lines: SW30 bit 2 is on.
Connection between multiple refrigerant 
lines: SW30 bit 2 of the connected header 
unit is turned on only for one line.
E19 ⇔ -02
Alternate 
blinking
When connecting an indoor/outdoor communication line 
between outdoor units under the condition of a connected 
communication line between outdoor units ( Fig. 2).
Correct wiring
E20 ⇔ -01
Alternate 
blinking
Address setup is performed with connecting an indoor/
outdoor communication line between outdoor units ( Fig. 3).
Correct wiring
Address setup is performed under the condition of 
connecting multiple refrigerant lines ( Fig. 3).
Correct wiring
ON
12
SW30
Indoor remote 
controller 
status
Header unit 
7-segment 
display
Cause Countermeasures
No response None
The communication line is not connected between indoor 
and outdoor (the unit that does not respond to the indoor 
remote controller).
Modify the wiring.
Line address and indoor address are not set (the unit that 
does not respond to the indoor remote controller).
Set up the address.
The power of the header unit of the group is not turned on in 
indoor group control (the unit that does not respond to the 
indoor remote controller).
Turn on the power.
Group address is set to the follower unit for individual control 
(the unit that does not respond to the indoor remote 
controller).
Set the group address to “0” in the case of 
individual control.
No display on the 
indoor remote 
controller (no line 
is output.)
None
The power is not turned on (the unit that is not displayed on 
the indoor remote controller).
Turn on the power.
The indoor remote controller is not connected with a wire (the 
unit that is not displayed on the indoor remote controller).
Modify the wiring.
Miswiring of the indoor remote controller (the unit that is not 
displayed on the indoor remote controller)
Modify the wiring.
Indoor remote controller communication circuit error (the unit 
that is not displayed on the indoor remote controller)
If 208/230 V is incorrectly applied to the indoor remote
controller terminal, the remote controller communication 
circuit fails.
Remove the fast-on terminal connected to 
indoor remote controller terminals A/B, and 
check the voltage. If voltage is not applied 
(normally 15 to 18 V), replace the PC board.