40
Fig. 25 — Typical Line Voltage Wiring Schematic (50XCA012-24, 208/230-3-60 Units Shown)
a50-8504
*Disconnect can be factory or field-installed.
NOTES:
1. Fan motors are inherently thermally protected.
2. Three-phase motors are protected under primary
single phase conditions.
3. Use conductors suitable for at least 194
°F (90°C)
when replacing factory wiring.
4. Use copper conductors only.
5. Wiring for field power supply must b
e rated at 165°F
(75°C) minimum.
6. Phase rotation sequence is L2-L1-L3.
7. TRAN1 and TRAN2 power separate 24-V circuits.
These circuits should not be interconnected and
separation must be maintained.
8. Transformers are factory wired for 240 v operation.
Move the black wire to the 208 v tap for 208 v
operation.
LEGEND
C — Compressor Contactor
CH — Crankcase Heater
CLO — Compressor Lockout
COMP — Compressor
CR — Control Rel
ay
DISC — Disconnect
FRZ — Freeze Protection
GND — Ground
HPS — High Pressure Switch
HR — Heat Relay
IFC — Indoor-Fan Contactor
IFM — Indoor-Fan Motor
IFR — Indoor-Fan Relay
LPS — Low Pressure Switch
LLT — Liquid Line Temperature
OFC — Outdoor-Fan Contactor
OFM — Outdoor-Fan Motor
OFR — Outdoor-Fan Relay
PRES — Pressure Transducer
SAT — Supply Air Thermistor
TB — Terminal Block
TRAN — Transformer
VFD — Variable Frequency Drive
Terminal Block Connectio
n
Marked Terminal
Unmarked Terminal
Splice
Factory Wiring
Field Power Wiring
LEGEND AND NOTES FOR FIG. 25-30
IFM
COMP1
12
BLK
12
BL
12
YE
11
BLK
12
BLU
11
YE
C1
12
BLK
12
BLK
C
1
TB1
CL
1-Loo
10
BLK
10
YE
10
BLU
10
BLK
10
YE
10
BL
10
GR
11
BLK
11
YE
11
BL
2
1
3
T2L2
T1L1
T3L3
15
BLK
15
YE
50
RED
50
BR
IF
IFR
DIS
1
L2
L3
L1
GN
10
BLK
10
BLK
10
BLK T3L3
T2L2
T1L1
11
BLK
11
YE
11
BL
11
GR
OFM
2
1
3
GND
12
GR
2
1
3
COMP2
13
BLK
13
BL
13
YE
12
BLK
12
BL
12
YE
C2
13
BLK
13
BLK
C
2
CL
2-Loo
T2L2
T1L1
T3L3
13
GR
2
1
3
15
BLK
15
YE
56
RED
56
BR
TB3
OF
OFR
T3L3
T2L2
T1L1
20
23
V
3
60 Hz
TRA
1
24 V
Class 2
20
V
24
V
COM
TRA
2
24 V
Class 2
20
V
24
V
COM
Continued
on Low
Voltage
Diagram