Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
Safety Considerations
Improper  installation,  adjustment,  alteration,  service,  maintenance,  or
use can cause explosion, fire, electrical shock, or other conditions which
may  cause  death,  personal  injury  or  property  damage.  Consult  a
qualified  installer,  service  agency,  or  your  distributor  or  branch  for
information  or  assistance.  The  qualified  installer  or  agency  must  use
factory-authorized  kits  or  accessories  when  modifying  this  product.
Refer  to  the  individual  instructions  packaged  with  kits  or  accessories
when installing.
Follow  all  safety  codes.  Wear  safety  glasses,  protective  clothing  and
work gloves. Have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in literature and
attached to the unit. Consult local building codes and the current editions
of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code
CSA C22.1.
Recognize safety information. This is the safety-alert symbol  . When
you see this symbol on the unit and in instruction manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION.
These words are used with the safety-alert symbol. DANGER identifies
the most serious hazards which will result in severe personal  injury or
death.  WARNING  signifies  hazards  which  could  result  in  personal
injury or  death.  CAUTION is  used  to identify unsafe  practices  which
may  result  in  minor  personal  injury  or  product  and  property  damage.
NOTE  is  used  to  highlight  suggestions  which  will  result  in  enhanced
installation, reliability, or operation.
Table of Contents
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Heater Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Air Ducts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 1 – Fan Speed Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Refrigerant Tubing Connection and Evacuation  . . . . . . . . . . . . . . . . . . 7
Refrigerant Flow-Control Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Start-Up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Care and Maintenance  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 2 – Air Delivery Performance Correction Component Pressure 
Drop (in. wc) at Indicated Airflow (Dry-to-Wet Coil) . . . . . . . . . . . . 9
Table 3 – Factory-Installed Filter Static Pressure Drop (in. wc) . . . . 9
Table 4 – Electric Heater Static Pressure Drop (in. wc). . . . . . . . . . 10
Table 5 – PF4MNP Airflow Performance (CFM) . . . . . . . . . . . . . . 10
Table 6 – PF4MNB Airflow Performance (CFM) . . . . . . . . . . . . . . 11
Introduction
PF4M models are R-410A Fan Coils designed for installation flexibility.
These units leave the factory  compliant with low leak requirements of
less than 2% cabinet leakage  rate at 0.5 inches W.C. and 1.4% cabinet
leakage  rate  at  0.5  inches  W.C.  when  tested  in  accordance  with
ASHRAE 193 standard.
A  TXV  is  used  on  PF4MNP  (018–060)  and  PF4MNB(019–061).  All
these fan coils use a multi-tap ECM motor for efficiency. The units have
be  designed  for  upflow,  downflow  (kit  required),  and  horizontal
orientations, including manufactured and mobile home applications.
These  units  require  a  field  supplied  air  filter,  and  are  designed
specifically  for  R-410A  refrigerant  air  conditioners  and heat pumps  as
shipped. These units are available for systems of 18,000 through 60,000
BTUh  nominal  cooling  capacity.  Factory-  authorized,  field  -  installed
electric  heater  packages  are  available  in  sizes  5  through  30kW.  See
Product Data literature for all available accessory kits.
Heater Packages
This unit may or may not be equipped with an electric heater package.
For  units not equipped  with factory-installed heat, a  factory-approved,
field-installed,  UL  listed  heater  package  is  available  from  your
equipment  supplier. See  unit rating  plate for  a  list of factory-approved
heaters. Heaters that are not factory approved could cause damage which
would not be covered under the equipment warranty. If fan coil contains
a  factory-installed  heater  package,  minimum  circuit  ampacity  (MCA)
and maximum fuse/breaker may be different than units with a same size
field-installed accessory heater. The differences is not an error and is due
to calculation difference per UL guidelines.
PF4MNB, PF4MNP
FAN COIL UNITS
SIZES 018 TO 061
WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to maintain proper clearances could result in personal injury or
death.
Before  installing  or  servicing  unit, always  turn  off all  power  to  unit.
There may be more than 1 disconnect switch. Turn off accessory heater
power if applicable. 
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury. 
Sheet  metal  parts  may  have sharp edges  or  burrs.  Use  care and wear
appropriate  protective  clothing,  safety  glasses  and  gloves  when
handling parts.