10.8 High Altitude Locations
Because the chiller is initially calibrated at sea level, it is necessary to recalibrate the pressure transducers if the
chiller has been moved to a high altitude location. Note that Atmospheric Pressure can be adjusted in the Service
Parameters Menu (located in the Configuration Menu).
See 5.9.1 section for calibration.
10.9 Quick Test
The Quick Test feature is located in the Main Menu. Use this feature to test chiller status, test the status of various
actuators, view water temperature deltas, and test pump and relays, as well as control inlet guide vane, envelop
control valve, alarms, condenser, and chilled water pumps. The tests can help to determine whether a switch is
defective or a relay is not operating, as well as other useful troubleshooting issues. During pumpdown operations,
the pumps are energized to prevent freeze-up and the vessel pressures and temperatures are displayed.
10.10 Quick Calibration
Use this menu to calibrate IGVs and the EC valve if it has feedback.
10.11 Pumpdown/Lockout
The Pumpdown/Lockout feature, available from the Maintenance Menu, prevents compressor start-up when there
is no refrigerant in the chiller or if the vessels are isolated. The Terminate Lockout feature ends the
Pumpdown/Lockout after the pumpdown procedure is reversed and refrigerant is added.

Table of Contents

Other manuals for Carrier PIC 5+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier PIC 5+ and is the answer not in the manual?

Carrier PIC 5+ Specifications

General IconGeneral
Input Voltage Range24 VDC
Relative Humidity Range5% to 95% non-condensing
Number of Universal Inputs8
Enclosure RatingIP20
Communication PortsRS-485
Storage Temperature Range-40°C to +85°C
Communication ProtocolModbus RTU

Related product manuals