1
55
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
[E04]
No
No
Ye s
Ye s
Ye s
Ye s
Ye s
Ye s
No
No
No
No
[E06]
S
ub-code: No. of indoor units which received si
g
nals normally
Check code
Check code
Check code name
C
heck code name
Cause
Cause
Dec
r
eased
n
u
m
be
r of in
d
oor
u
nit
s
Indoor/Outdoor communication
circuit error
(Detected at indoor side)
1
. Communication lines
(
U1, U2
)
connection error
be
tw
ee
n in
d
oor
a
n
d
o
u
t
d
oor
2
.
C
ommunication connector's connection error on
indoor unit
,
error on P.C. board
3
.
C
ommunication connector's connection error on
outdoor unit
,
error on I/F board
4
. Power suppl
y
of indoor unit (Is power turned on?)
1. Power of outdoor unit was firstly turned on.
2. Connection error of communication line between
indoor and outdoor
3. End terminal resistance setup error on
communication between indoor and outdoor
4. Address setup error
Is there no
miswiring/disconnection
on communication line
between indoor and
outdoor?
Was power turned on
in order of indoor unit
outdoor unit?
Is connection
(U1/U2 terminals) of
indoor/outdoor inter-unit
wire normal?
Is connector
connection from U1/U2
terminals of indoor/outdoor
inter-unit wire
normal?
Is the end terminal
resistance setup of outdoor
unit normal?
Is power applied to fuse
(F03) on indoor P.C.
board?
Is address setup correct?
Is there no noise, etc?
Is connection
of CN40 connector on
indoor P.C. board
normal?
Is connection of CN01
connector on outdoor I/F
P.C. board normal?
Is power of indoor unit
turned on?
Did a power failure
occur?
Is there no noise, etc?
Correct communication line.
Turn on power again in order
of indoor unit outdoor unit.
Correct inter-unit wire.
Correct connector connection.
Correct the end terminal
resistance setup.
Set up address again.
Check noise, etc, and
eliminate it if any.
Check connection of inter-unit
wire between indoor and outdoor
is correct, and then connect
communication line connector on
indoor P.C. board (CN40) to
CN44 (EMG).
Correct wiring or connector.
Turn on power of indoor unit.
Clear the check code.
Check noise, etc, and eliminate
it if any.
Check indoor P.C. board.
Defect Replace
Check indoor P.C. board.
Defect Replace
(NOTE)
1. When signal is not sent for a certain period from the indoor unit which has
used to send signals normally, [E06] is displayed.
For details, refer to "8-5. Troubleshooting in Test Operation ".

Table of Contents