– 92 –
Group address
Individual: 0000
Header unit: 0001
Follower unit: 0002
(Wiring example for 2 refrigerant lines)
Line 1 Line 2
Line 1 Line 2
Outdoor
Indoor 1 Indoor 2Indoor 1
(Remote controller group control)
Indoor 2 Indoor 3
Indoor 1 Indoor 2Indoor 1 Indoor 2 Indoor 3
Line address
Indoor address
1
1
1
Header
1
2
2
Follower Follower Follower Follower
1
3
2
2
1
2
2
2
2
Outdoor
OutdoorOutdoor
(Wiring during manual address setup)
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Group
address
In the above example, where remote controllers are not
yet wired, set the address manually after individually
connecting the wired remote controller.
After address setup, return to the original
wiring over remote controllers.
In cases of
remote controller
group control
Manual address setup from the remote controller
With indoor wiring work completed and outdoor wiring work not done—in cases where indoor unit addresses are
decided in advance from the wired remote controller, or in cases where addresses are change after address setup.
1 Arrange one indoor unit and one remote
controller set to 1 by 1.
2 Turn on the power.
3 Push the + + buttons simultaneously for
4 seconds or more.
LCD begins blinking.
(Refrigerant line address)
4 Using the buttons, set the DN code to
1212
1212
12.
5 Using the buttons, set up the line address
(match it with the line address on the interface
PC board of the header unit on the same
refrigerant line).
6 Push the button (OK when the display goes
on).
(Indoor address)
7 Using the buttons, set the DN code to
1313
1313
13.
8 Using the buttons, set up the indoor
address.
(
00010001
00010001
0001 ~
00400040
00400040
0040)
9 Push the button (OK when the display goes
on).
(Group address)
10
Using the buttons, set the DN code to
1414
1414
14.
11
Using the buttons, set Individual =
00000000
00000000
0000,
Header unit =
00010001
00010001
0001, Follower unit =
00020002
00020002
0002.
12
Push the button (OK when the display goes
on).
(Central control address)
13
Using the buttons, set DN code to
0303
0303
03.
14
Using the buttons, set up the central
control address.
(
00010001
00010001
0001 ~
00640064
00640064
0064)
15
Push button. (OK when display goes on).
16
Push the button.
Setup is finished (“Setting up” blinks; when “Setting up”
goes off, operation is possible).
17
Return to the original wiring over remote
controllers.
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
DN code
(CODE No.)
Set
data
5, 8, 11, 14
6, 9, 12, 15
16
4
7
10
13
3