Table 5 -- Menu Structure
a
(cont)
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
b
EXPANDED PARAMETER NAME
Notes
STA TUS
(cont )
EXH2 OUT OFF ON/OFF EXHAUST STA GE 2 RELAY OUTPUT
Output of AUX1 O term inal Dis plays ON when damp e r position reac he s
programmed percentage setpoi nt
ON = 24 Vac Output, OFF = No Output; displays only if A UX1 O =
EXH2
ERV OFF ON/OFF ENERGY RECOVERY UNIT RELA Y OUTPUT
Out put of A UX1 O term inal, ON = 24 Vac Outp ut , O FF = No Output;
di splays only if AUX1 O = ERV
MECH COOL ON
or
HEAT S TAGES ON
0 0, 1, or 2 Displays s t a g e of mecha nical cooli ng that is ac t ive.
Displays the st a g e of heat pump heating that is active
FAN SPEED n/a LOW or HIGH SUPP LY FAN SPEED
Displays speed setting of fan on a 2 ---speed fan unit.
W(HEATON) n/a ON/OFF HEAT DEMAND STATUS
Displays s t a t us of heat dem and on a 2---spe e d fan unit .
SETPOINTS
MAT SET 53_F
(12_C)
38 to 70_F;
(3 to 21_C)
increment by 1
SUPPLY AIR SETPO I NT
Setpoi nt determines where the economizer will modulate the OA damper to
maintain the mixed air temperature.
SeeMenuNote2.
LOW T LOCK 32_F
(0_C)
---45 to 80_F;
(---43 to 27_C)
increment by 1
COMPRESSOR LOW TEMPERATURE LOCKOUT
Setpoi nt determines outdoor temperature when the mechanic al cooling
canno t be turned on. Comm only referre d to as the Comp ressor locko ut . A t
or below the se t point the Y1---O and Y2---O will not be energized on the
cont ro lle r.
DRYBLB SET 63_F
(17_C)
48 to 80_F
(9 to 27_C)
increment by 1
OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT
Setpoi nt determines where the economizer will assume outdoor air
temperature is good for free cooling; e.g.: at 63_F(17_C), unit will
economize at 62_F (16.7_C ) and below and not economize at 64_F
(17.8_C) and above. There is a 2_F(1.1_C)deadband.
SeeMenuNote3
ENTH CURVE ES3 ES1, ES2, ES3, ES4, or
ES5
ENTHALPY CHANGEOVER CURVE
(Re q uires enthalp y se ns o r opt ion)
Enthalp y bo und ar y “curv e s ” for econo m izing using sing le ent halpy .
See pag e 22 for de s c ription of entha lp y curve s .
DCV SET 1100ppm 500 to 2000 ppm;
increment by 100
DEMA N D CONTR OL VENTILATI O N SETPOINT
Displays only if CO
2
se nsor is co nne c ted. Setp o int for Demand Contro l
Ventilation of space. Above the setpoint, the OA dampers will modulate
open to bring in additional OA to maintain a space ppm level below the
setpoint.
MIN POS 2.8 V 2to10Vdc
VENTILATION MINIMUM POSITION
Displays O NLY if a CO
2
se nsor is NOT connected.
Wit h 2 ---sp eed fan units MIN PO S L (low sp eed fan) and MIN POS H (high
speed fan) setti ngs are required. Default for MIN POS L is 3.2V and MIN
POS H is 2.8V.
VENTMAX 2.8 V
2to10Vdc DCV MA XIMUM DAMPER POSITI ON
Displays only if a CO2 sensor is connected. Used for Vbz (ventilation max
cfm) setpoint. VENTMAX is the same setting as MIN POS would be if you
did not have the CO2 se nsor.
100 to 9990 cfm
increment by 10
If OA, MA RA and CO2 sens ors are connected and DCV CAL ENABLE is
set to AUTO mode, the OA dampe rs are controlled by CFM and di s plays
from 100 to 9990 cfm.
2to10Vdc W it h 2 ---speed fan units VENTMA X L (low speed fan) and VENTMAX H
(high speed fan) settings are required. Default for VENTMAX L is 3.2V and
VENTMAX H is 2.8V.
VENTMIN 2.25 V
2to10Vdc DCV MINIMUM DAMPER POSITION
Disp lays only if CO2 sensor is connected . Used for Va (venti lation min cfm)
se t point . This is the vent ilati on req ui re m e nt for less than maxim um
oc c upancy of the sp a c e .
100 to 9990 cfm
increment by 10
If OA, MA RA and CO2 sens ors are connected and DCV CAL ENABLE is
set to AUTO mode, the OA dampe rs are controlled by CFM and di s plays
from 100 to 9990 cfm.
2to10Vdc With 2---speed fan units VENTMIN L (low speed fan) and VENTMIN H
(high speed fan) settings are required. Default for VENTMIN L is 2.5V
and VENTMIN H is 2.25V.
ERV OAT SP
d
32_F
(0_C)
0to50_F;
(---18 TO 10_C)
increment by 1
ENERGY RECOVERY VENTILATION UNIT OUTDOOR AIR TEMPERATURE
SETPOI NT
Only when AUX1 O = ERV
EXH1 SET 50% 0 to 100% ;
Increment by 1
EXHAUST FAN STAGE 1 SETPOINT
SetpointforOAdamperpositionwhenexhaustfan1ispoweredbythe
economizer.
Wit h 2 ---speed fan unit s Exh1 L (low speed fan) and Exh1 H (high speed
fan) settings are required. Default for Exh1 L is 65% and Exh1 H is 50%
SUP--TI24--02SI