18
CONVENIENCE OUTLETS
Two types of convenience outlets are offered on 48FC
models: non-powered and unit-powered. Both types provide a
125-volt GFCI (ground-fault circuit interrupter) duplex re-
ceptacle rated at 15A behind a hinged waterproof access cov-
er, located on the end panel of the unit. See Fig. 29.
Fig. 30 shows the Convenience Outlet Utilization label
which is located below the convenience outlet.
Fig. 29 — Convenience Outlet Location
Fig. 30 — Convenience Outlet Utilization
Notice Label
NOTE: Unit powered convenience outlets are not available as
factory installed options for single phase (-3 voltage code
models).
Installing Weatherproof Cover
A weatherproof while-in-use cover for the factory-installed con-
venience outlets is now required by UL standards. This cover
cannot be factory-mounted due its depth; it must be installed at
unit installation. For shipment, the convenience outlet is covered
with a blank cover plate.
On units with electro-mechanical controls the weather-
proof cover kit is shipped in the unit’s control box. The kit in-
cludes the hinged cover, a backing plate, and gasket. On units
with a factory installed direct digital controller (SystemVu™
or RTU Open) the weatherproof cover kit is secured to the
basepan underneath the control box (see Fig. 31). 
Fig. 31 — Weatherproof Cover — Shipping Location 
on Units with Factory Installed DDC
1. Remove the blank cover plate at the convenience outlet;
discard the blank cover.
2. Loosen the two screws at the GFCI duplex outlet, until
approximately 
1/
2
 in. (13 mm) under screw heads is
exposed. Press the gasket over the screw heads.
3. Slip the backing plate over the screw heads at the key-
hole slots and align with the gasket; tighten the two
screws until snug (do not over-tighten).
4. Mount the weatherproof cover to the backing plate as
shown in Fig. 32.
5. Remove two slot fillers in the bottom of the cover to per-
mit service tool cords to exit the cover.
6. Check for full closing and latching.
Fig. 32 — Weatherproof Cover Installation
Non-Powered Convenience Outlet
This type requires the field installation of a general-pur-
pose 125v 15A circuit powered from a source elsewhere in
WARNING
Failure to follow this caution could result in personal injury
or death.
Units with convenience outlet circuits may use multiple dis-
connects. Check convenience outlet for power status before
opening unit for service. Locate its disconnect switch, if ap-
propriate, and open it. Lock-out and tag-out this switch, if
necessary.
CONVENIENCE
OUTLET GFCI
PWD-CO FUSE
SWITCH
PWD-CO
TRANSFORMER
WARNING
Failure to follow this caution could result in personal injury
or death.
Disconnect all power to unit and convenience outlet. Lock-
out and tag-out all power prior to installation.
COVER - WHILE-IN-USE
WEATHERPROOF
BASEPLATE FOR
GFCI RECEPTACLE
GASKET
GFCI RECEPTACLE
NOT INCLUDED
TOP
TOP
TOP
WET  LOCATIONS
WET  L O
CATIONS