WEIGHTS & DIMENSIONS (cont.)
C09557A
Fig. 12 -- Dimensions 50TCQ 12
C
B
A
D
C08337
Fig. 13 -- Service Clearance
LOC DIMENSION CONDITION
A
48---in. (1219 mm) Unit disconnect is mounted on panel
18---in. (457 mm) No disconnect, convenience outlet option
18---in. (457 mm) Recommended service clearance
12---in. (305 mm) Minimum clearance
B
42---in. (1067 mm) Surface b ehind servicer is grounded (e.g ., metal, masonry wall)
36---in. (914 mm) Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)
Special Check for sources of flue products within 10--- ft of unit fresh air intake hood
C
36---in. (914 mm) Side condensate drain is used
18---in. (457 mm) Minimum clearance
D
42---in. (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
36---in. (914 mm) Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)
50TCQ