48
Table 18 HEATING CAPACITY 5 TONS
50TCQ06
RETURN
AIR
(°FDB)
CFM
(STANDARD AIR)
TEMPERATURE AIR ENTERING OUTDOOR COIL (°F db AT 70% RH)
--- 1 0 0 10 17 30 40 47 50 60
55
1500
Capacity 22.7 28.3 34.2 38.6 47.4 54.3 60.0 62.6 70.3
Int. Cap. 21.0 26.1 31.4 35.2 41.5 54.3 60.0 62.6 70.3
2000
Capacity 22.8 28.5 34.4 38.9 47.9 55.3 60.9 63.1 70.9
Int. Cap. 21.1 26.2 31.6 35.4 42.0 55.3 60.9 63.1 70.9
2500
Capacity 24.2 30.0 35.9 40.4 49.6 56.9 62.3 64.4 72.0
Int. Cap. 22.4 27.6 33.0 36.8 43.5 56.9 62.3 64.4 72.0
70
1500
Capacity 19.9 25.8 31.9 36.3 45.2 51.7 57.6 60.0 67.9
Int. Cap. 18.4 23.7 29.3 33.1 39.6 51.7 57.6 60.0 67.9
2000
Capacity 20.1 26.1 32.3 36.7 45.8 52.9 58.4 61.0 68.8
Int. Cap. 18.6 24.0 29.6 33.5 40.1 52.9 58.4 61.0 68.8
2500
Capacity 21.5 27.6 33.8 38.3 47.5 54.7 60.4 62.7 70.2
Int. Cap. 19.9 25.4 31.1 35.0 41.6 54.7 60.4 62.7 70.2
80
1500
Capacity 17.6 23.7 30.0 34.6 43.5 50.2 55.7 58.2 66.1
Int. Cap. 16.3 21.9 27.6 31.5 38.1 50.2 55.7 58.2 66.1
2000
Capacity 17.8 24.1 30.5 35.1 44.3 51.2 56.6 59.4 67.2
Int. Cap. 16.5 22.2 28.0 32.0 38.8 51.2 56.6 59.4 67.2
2500
Capacity 19.3 25.6 32.1 36.8 46.0 53.1 58.8 61.1 68.8
Int. Cap. 17.8 23.6 29.4 33.5 40.3 53.1 58.8 61.1 68.8
--- Indicates standard rating point
LEGEND
Capacity --- Instantaneous Capacity (1000 Btuh) includes indoor fan motor heat @AHRI static conditions
Int. Cap. --- Integrated Capacity is Instantaneous Capacity minus the effects of frost on the outdoor coil and the heat
required to defrost
RH --- Relative Humidity
d b --- D r y B u l b
Table 19 HEATING CAPACITY 6 TONS
50TCQ07
RETURN
AIR
(°FDB)
CFM
(STANDARD AIR)
TEMPERATURE AIR ENTERING OUTDOOR COIL (°F db AT 70% RH)
--- 1 0 0 10 17 30 40 47 50 60
55
1800
Capacity 22.4 29.8 37.1 42.5 53.5 62.4 68.6 71.2 80.3
Int. Cap. 20.7 27.4 34.1 38.8 46.9 62.4 68.6 71.2 80.3
2400
Capacity 24.6 32.1 39.6 45.1 56.4 65.6 71.5 74.2 83.8
Int. Cap. 22.7 29.5 36.3 41.1 49.4 65.6 71.5 74.2 83.8
3000
Capacity 27.4 35.0 42.5 48.2 59.5 68.6 74.5 77.2 86.8
Int. Cap. 25.3 32.2 39.0 43.9 52.1 68.6 74.5 77.2 86.8
70
1800
Capacity 17.7 25.5 33.2 38.6 49.5 58.5 65.0 67.7 76.5
Int. Cap. 16.4 23.5 30.5 35.2 43.4 58.5 65.0 67.7 76.5
2400
Capacity 19.9 27.9 35.8 41.4 52.7 62.0 68.4 71.0 80.3
Int. Cap. 18.4 25.7 32.9 37.7 46.2 62.0 68.4 71.0 80.3
3000
Capacity 22.8 30.9 38.9 44.5 56.1 65.5 71.7 74.4 83.9
Int. Cap. 21.1 28.4 35.7 40.6 49.2 65.5 71.7 74.4 83.9
80
1800
Capacity 13.9 21.9 29.9 35.5 46.2 55.3 62.0 64.9 73.7
Int. Cap. 12.8 20.2 27.4 32.3 40.5 55.3 62.0 64.9 73.7
2400
Capacity 16.0 24.4 32.6 38.4 49.6 59.0 65.8 68.6 77.5
Int. Cap. 14.8 22.5 29.9 35.0 43.5 59.0 65.8 68.6 77.5
3000
Capacity 18.8 27.4 35.8 41.6 53.1 62.7 69.4 72.1 81.4
Int. Cap. 17.4 25.2 32.8 37.9 46.6 62.7 69.4 72.1 81.4
--- Indicates standard rating point
LEGEND
Capacity --- Instantaneous Capacity (1000 Btuh) includes indoor fan motor heat @AHRI static conditions
Int. Cap. --- Integrated Capacity is Instantaneous Capacity minus the effects of frost on the outdoor coil and the heat
required to defrost
RH --- Relative Humidity
d b --- D r y B u l b
50TCQ