50
Table 22 HEATING CAPACITY 10 TONS
50TCQD12
RETURN
AIR
(°Fdb)
CFM
(STANDARD AIR)
TEMPERATURE AIR ENTERING OUTDOOR COIL (°F db AT 70% RH)
--- 1 0 0 10 17 30 40 47 50 60
55
3000
Capacity 41.8 52.4 64.1 72.8 90.4 105.3 118.0 121.9 140.3
Int. Cap. 38.7 48.2 58.8 66.3 79.2 105.3 118.0 121.9 140.3
4000
Capacity 43.3 54.0 66.0 74.5 92.7 107.8 120.2 124.1 142.1
Int. Cap. 40.0 49.7 60.6 68.0 81.2 107.8 120.2 124.1 142.1
5000
Capacity 46.9 57.7 69.7 78.2 96.6 111.5 123.5 127.3 142.3
Int. Cap. 43.3 53.1 64.0 71.3 84.6 111.5 123.5 127.3 142.3
70
3000
Capacity 37.4 48.2 59.7 68.5 86.2 100.6 113.0 117.1 135.3
Int. Cap. 34.6 44.4 54.8 62.4 75.5 100.6 113.0 117.1 135.3
4000
Capacity 39.0 49.9 61.6 70.7 88.5 103.3 115.9 119.8 137.6
Int. Cap. 36.1 45.9 56.6 64.5 77.5 103.3 115.9 119.8 137.6
5000
Capacity 42.6 53.7 65.5 74.8 92.5 107.5 119.6 123.4 140.6
Int. Cap. 39.4 49.4 60.1 68.2 81.1 107.5 119.6 123.4 140.6
80
3000
Capacity 33.9 44.8 56.5 65.1 83.2 97.3 109.5 113.4 131.6
Int. Cap. 31.4 41.3 51.8 59.3 72.9 97.3 109.5 113.4 131.6
4000
Capacity 35.5 46.6 58.5 67.3 85.5 100.0 112.5 116.5 134.2
Int. Cap. 32.8 42.9 53.7 61.4 75.0 100.0 112.5 116.5 134.2
5000
Capacity 39.1 50.4 62.3 71.3 89.6 104.3 116.6 120.4 137.5
Int. Cap. 36.2 46.4 57.2 65.0 78.5 104.3 116.6 120.4 137.5
--- Indicates standard rating point
LEGEND
Capacity --- Instantaneous Capacity (1000 Btuh) includes indoor fan motor heat @AHRI static conditions
Int. Cap. --- Integrated Capacity is Instantaneous Capacity minus the effects of frost on the outdoor coil and the heat
required to defrost
RH --- Relative Humidity
d b --- D r y B u l b
Table 23 HEATING CAPACITY 12.5 TONS
50TCQD14
RETURN AIR
(°FdB)
CFM (STANDARD AIR)
TEMPERATURE AIR ENTERING OUTDOOR COIL (°F db AT 70% RH)
--- 1 0 0 10 17 30 40 47 50 60
55
3750
Capacity 33.7 47.5 69.8 83.1 109.3 131.7 149.7 155.6 180.1
Int. Cap. 31.2 43.7 64.0 75.8 95.8 131.7 149.7 155.6 180.1
5000
Capacity 35.7 49.7 72.4 85.8 112.9 136.1 152.9 158.1 178.7
Int. Cap. 33.0 45.7 66.5 78.2 99.0 136.1 152.9 158.1 178.7
6250
Capacity 38.9 53.0 76.2 89.5 117.1 139.4 153.5 158.0 175.6
Int. Cap. 36.0 48.8 70.0 81.6 102.6 139.4 153.5 158.0 175.6
70
3750
Capacity 24.4 38.2 59.4 73.1 99.8 121.2 138.5 144.5 169.7
Int. Cap. 22.6 35.2 54.5 66.7 87.4 121.2 138.5 144.5 169.7
5000
Capacity 26.4 40.4 62.1 76.6 103.2 125.4 143.0 148.6 170.3
Int. Cap. 24.4 37.2 57.0 69.8 90.4 125.4 143.0 148.6 170.3
6250
Capacity 29.6 43.8 65.9 80.7 107.3 129.8 145.5 150.4 169.1
Int. Cap. 27.3 40.3 60.5 73.6 94.0 129.8 145.5 150.4 169.1
80
3750
Capacity 17.5 31.4 52.6 65.6 93.3 114.2 131.1 137.0 162.4
Int. Cap. 16.2 28.9 48.3 59.8 81.8 114.2 131.1 137.0 162.4
5000
Capacity 19.3 33.4 55.2 68.7 96.6 118.2 135.7 141.5 164.0
Int. Cap. 17.8 30.8 50.7 62.6 84.6 118.2 135.7 141.5 164.0
6250
Capacity 22.4 40.3 58.8 72.7 100.6 122.6 139.3 144.3 163.8
Int. Cap. 20.7 37.1 54.0 66.3 88.2 122.6 139.3 144.3 163.8
--- Indicates standard rating point
LEGEND
Capacity --- Instantaneous Capacity (1000 Btuh) includes indoor fan motor heat @AHRI static conditions
Int. Cap. --- Integrated Capacity is Instantaneous Capacity minus the effects of frost on the outdoor coil and the heat
required to defrost
RH --- Relative Humidity
d b --- D r y B u l b