48
EVAPORATOR-FAN MOTOR DATA — HIGH-STATIC MOTORS
LEGEND
Bhp —
Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the
motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not
result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
OUTDOOR SOUND POWER (TOTAL UNIT)
LEGEND
ECONOMIZER STATIC PRESSURE DROP (in. wg)
48HJ004-007
ECONOMIZER STATIC PRESSURE DROP (in. wg)
48HJ008-014
UNIT
48HJ
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
UNIT VOLTAGE
MAXIMUM
AMP DRAW
004
Three 2.40 2120
208/230 6.4
460 2.9
575 2.9
005
Three 2.40 2120
208/230 6.4
460 2.9
575 2.9
006
Three 2.90 2615
208/230 7.9
460 3.6
575 3.6
007
Three 2.90 2615
208/230 6.4
460 3.6
575 3.6
008,009
Three 4.20 3775
208/230 12.6
460 5.7
575 5.7
012
Three 5.25 4400
208/230 15.0
460 7.4
575 7.4
UNIT
48HJ
ARI
RATING
(Bels)
OCTAVE BANDS
63 125 250 500 1000 2000 4000 8000
004,005
7.6 55.9 66.0 64.0 66.2 68.4 64.5 61.7 57.3
006,007
8.0 59.1 68.9 68.7 71.9 74.0 68.9 65.7 59.0
008,009
8.2 62.2 69.3 71.5 74.7 76.2 72.9 68.7 61.5
012
8.4 64.6 71.1 73.3 76.9 77.6 73.7 70.6 63.7
014
8.6 63.7 69.9 72.5 78.2 81.1 77.3 73.3 66.8
ARI —
Air Conditioning and Refrigeration Institute
Bels —
Sound Levels (1 bel = 10 decibels)
UNIT
CFM
900 1200 1400 1600 1800 2000 2200 2400 2600
Durablade
0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05
EconoMi$er
— 0.09 0.12 0.15 0.19 0.24 0.29 0.35 —
UNIT
CFM
2200 2500 3000 3500 4000 4500 5000 5500 6000
Durablade
.02 .02 0.030 0.040 0.05 0.06 0.07 0.08 0.09
EconoMi$er
——0.125 0.180 0.27 0.34 0.40 ——
Performance data (cont)