CL-17
INSTRUCTIONS
Fill in the table to indicate the unit design information (from submittal), required control configuration, or set point if these parameters
are to be configured as part of factory start-up. If left blank, the unit will be left at the default configuration and set points.
Unit Operating Configuration
Operating Setpoints
ITEM REQUIRED CONFIGURATION OR SET POINT VALUE
Control Type VAV RAT / TSTAT / SPT
Supply Fan Ctrl Continuous / Auto
Supply Fan Type SAV / VAV / CV
Supply Air CFM
Supply Fan ESP
Supply Fan rpm
SF Max Speed % (SP.MX)
SF Min Speed % (SP.MN)
SF Heat Min Speed % (HT.V.M)
SAV Dehum No / Yes
3rd Party Fan Ctrl No / Reset Ctrl / Override Ctrl
Duct Static Reset No / Yes
Exhaust Fan Type None / CV / Mod (BP)
Exhaust Fan CFM
Exhaust Fan ESP
Exhaust Fan rpm
Dehum Control Return Air RH / Dehum Input
SAT Reset No / Yes
Economizer Ctrl DB / Enth / Diff DB / Diff Enth
Econo Min Position % (EC.MN)
Econo Max Position % (EC.MX)
Econo Min SP.MN % (EP.MS)
Econo Min SP.MX % (EP.XS)
3rd Party Econo Ctrl No / Reset Ctrl / Override Ctrl
Field CO
2
Sens No / Yes
Remote Occ Switch No / Yes
Fire/Smoke/Purge No / Yes
Filter Status Switch No / Yes
Demand Limit Ctrl No / Yes
BACnet Comm No / Yes
Occupancy Control Schedule / BAS / Switch
ITEM REQUIRED CONFIGURATION OR SET POINT VALUE
Occ Heat SP °F (OHSP)
Unocc Heat SP °F (UHSP)
Heating SAT SP °F (HT.SP)
Lo Heat On Dmnd °F (L.H.ON)
Hi Heat On Dmnd °F (H.H.ON)
Low Heat Off Dmnd °F (L.H.OF)
Heat/Cool SP Gap °F (GAP)