Fig. 14 — Humidi-MiZer System Control
Fig. 15 — Humidi-MiZer System Diagram
Temperature Compensated Start
This logic is used when the unit is in the unoccupied state. The
control will calculate early Start Bias time based on Space Tem-
perature deviation from the occupied cooling and heating set
points. This will allow the control to start the unit so that the space
is at conditioned levels when the occupied period starts. This is re-
quired for ASHRAE 90.1-2016 compliance. A space sensor is re-
quired for non-linkage applications.
SETTING UP THE SYSTEM
The settings for temperature compensated start can be found in the
local display under Configuration
UNIT.
TCST-Cool Factor (TCS.C)
This is the factor for the start time bias equation for cooling.
TCST-Heat Factor (TCS.H)
This is the factor for the start time bias equation for heating.
NOTE: Temperature compensated start is disabled when these
factors are set to 0.
TEMPERATURE COMPENSATED START LOGIC
The following conditions must be met for the algorithm to run:
Unit is in unoccupied state.
Next occupied time is valid.
Current time of day is valid.
Valid space temperature reading is available (sensor or
DAV-Linkage).
Evaporator Discharge Temperature
In Subcool or Reheat Mode, compressor staging
and increased subcooling drives evaporator
discharge temperature down to meet higher latent
loads
Airflow
EVAPORATOR
HUMIDI-MIZER ADAPTIVE
DEHUMIDIFICATION
SYSTEM COIL
Supply Air Temperature Control
Innovative algorithm to control supply air temperature
modulates flow bypass to meet desired supply air setpoint -
no overcooling or overheating of the space.
Subcooling Mode: Meet Cooling Mode Supply Air Setpoint
Reheat Mode: Meet Return Air Offset or Reheat Setpoint (configurable)
CCT
SAT
D.C.SP COOL
RAT-D.V.RA or
D.V.HT
or SASPHT
3
4
EXPANSION
INDOOR AIR
EVAPORATOR
5
5'
EVAPORATOR
REHEAT HX
EXPANSION
DEVICE
4'
3'
CHECK VALVE
3-WAY VALVE
3a'
2'
2a'
BYPASS
MODULATING
VALVE
CONDENSER
OUTDOOR AIR
CONDENSER
MODULATING
VALVE
1'
COMPRESSOR
1
2
CONDENSER
OUTDOOR AIR
COMPRESSOR
CIRCUIT B
CIRCUIT A
ITEM EXPANSION RANGE UNITS CCN POINT
TCS.C Temp.Cmp.Strt.Cool Factr 0 to 60 min TCSTCOOL
TCS.H Temp.Cmp.Strt.Heat Factr 0 to 60 min TCSTHEAT