CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM EXPANSION RANGE DEFAULT SETTING
BP BUILDING PRESS. CONFIGS
BP.CF Building Press. Config 0 to 5 (multi-text strings) 0
BP.S Building Pressure Sensor Enable/Disable Disable
BP.R Bldg. Press. (+/-) Range 0.10 to 0.25 "H2O 0.25
BP.SP Building Pressure Setp. –0.25 to 0.25 "H2O 0.05
BP.SO BP Setpoint Offset 0 to 0.5 "H2O 0.05
BP.P1 Power Exhaust On Setp.1 0 to 100% 25
BP.P2 Power Exhaust On Setp.2 0 to 100% 75
B.V.A VFD/ACTUATOR CONFIG
B.V.ABP.FS VFD/Act. Fire Speed/Pos. 0 to 100% 100
B.V.ABP.MN VFD/Act. Min.Speed/Pos. 0 to 50% 0
B.V.ABP.MX VFD Maximum Speed 50 to 100% 100
B.V.ABP.1M BP 1 Actuator Max Pos. 85 to 100% 100
B.V.ABP.2M BP 2 Actuator Max Pos. 85 to 100% 100
B.V.ABP.CL BP Hi Cap VFD Clamp Val. 5 to 25% 10
FAN.T FAN TRACKING CONFIG
FAN.TFT.CF Fan Track Learn Enable Yes/No No
FAN.TFT.TM Fan Track Learn Rate 5-60 min 15
FAN.TFT.ST Fan Track Initial DCFM –20000 to 20000 CFM 2000
FAN.TFT.MX Fan Track Max Clamp 0 to 20000 CFM 4000
FAN.TFT.AD Fan Track Max Correction 0 -20000 CFM 1000
FAN.TFT.OF Fan Track Internl EEPROM –20000 to 20000 CFM 0
FAN.TFT.RM Fan Track Internal RAM –20000 to 20000 CFM 0
FAN.TFT.RS Fan Track Reset Internal Yes/No No
FAN.TSCF.C Supply Air CFM Config 1 to 2 (multi-text strings) 1
B.PID BLDG.PRESS.PID CONFIGS
B.PIDBP.TM Bldg.Pres.PID Run Rate 5 to 120 sec 10
B.PIDBP.P Bldg.Press. Prop. Gain 0 to 5 0.5
B.PIDBP.I Bldg.Press. Integ. Gain 0 to 2 0.5
B.PIDBP.D Bldg.Press. Deriv. Gain 0 to 5 0.3
ACT.C BLDG.PRES. ACTUATOR CFGS
ACT.CBP.1 BLDG.PRES. ACT.1 CONFIGS
ACT.CBP.1SN.1 BP 1 Serial Number 1 0 to 9999 0
ACT.CBP.1SN.2 BP 1 Serial Number 2 0 to 6 0
ACT.CBP.1SN.3 BP 1 Serial Number 3 0 to 9999 0
ACT.CBP.1SN.4 BP 1 Serial Number 4 0 to 254 0
ACT.CBP.1C.A.LM BP1 Cntrl Angle Lo Limit 0 to 90 35
ACT.CBP.2 BLDG.PRES. ACT.2 CONFIGS
ACT.CBP.2SN.1 BP 2 Serial Number 1 0 to 9999 0
ACT.CBP.2SN.2 BP 2 Serial Number 2 0 to 6 0
ACT.CBP.2SN.3 BP 2 Serial Number 3 0 to 9999 0
ACT.CBP.2
SN.4 BP 2 Serial Number 4 0 to 254 0
ACT.CBP.2C.A.LM BP2 Cntrl Angle Lo Limit 0 to 90 35
D.LV.T COOL/HEAT SETPT. OFFSETS
L.H.ON Dmd Level Lo Heat On –1 to 2 ^F 1.5
H.H.ON Dmd Level(+) Hi Heat On 0.5 to 20.0 ^F 0.5
L.H.OF Dmd Level(-) Lo Heat Off 0.5 to 2.0 ^F 1.0
L.C.ON Dmd Level Lo Cool On –1 to 2 ^F 1.5
H.C.ON Dmd Level(+) Hi Cool On 0.5 to 20.0 ^F 0.5
L.C.OF Dmd Level(-) Lo Cool Off 0.5 to 2.0 ^F 1.0
C.T.LV Cool Trend Demand Level 0.1 to 5.0 ^F 0.1
H.T.LV Heat Trend Demand Level 0.1 to 5.0 ^F 0.1
C.T.TM Cool Trend Time 30 to 600 sec 120
H.T.TM Heat Trend Time 30 to 600 sec 120
DMD.L DEMAND LIMIT CONFIG.
DM.L.S Demand Limit Select 0 to 3 (multi-text strings) 0
D.L.20 Demand Limit at 20 ma 0 to 100% 100
SH.NM Loadshed Group Number 0 to 99 0
SH.DL Loadshed Demand Delta 0 to 60% 0
SH.TM Maximum Loadshed Time 0 to 120 min 60
D.L.S1 Demand Limit Sw.1 Setpt. 0 to 100% 80
D.L.S2 Demand Limit Sw.2 Setpt. 0 to 100% 50