47
C.TYP = 3 (TSTAT – MULTI)
This configuration will force the control to monitor the
thermostat inputs to make a determination of mode. Unlike
traditional 2-stage thermostat control, the unit is allowed to
use multiple stages of cooling control and perform VAV-
type operation. The control will be able to call out a LOW
COOL or a HIGH COOL mode and maintain a low or high
cool supply air set point.
C.TYP = 4 (SPT – MULTI)
This configuration will force the control to monitor a space
temperature sensor to make a determination of mode. Un-
like traditional 2-stage space temperature control, the unit
is allowed to use multiple stages of cooling control and
perform VAV-type operation. The control will be able to
call out a LOW COOL or a HIGH COOL mode and main-
tain a low or high cool supply air set point.
Unit Size (SIZE)
There are several unit sizes (tons) for the P Series control. Make
sure this configuration matches the size called out by the model
number of the unit. This is important as the cooling stage tables
are directly determined based on the SIZE configuration.
Fan Mode (FN.MD)
The Fan Mode configuration can be used for machine control
types (Configuration
UNIT
C.TYP) 3 and 4. The Fan Mode
variable establishes the operating sequence for the supply fan
during occupied periods. When set to 1 (Continuous), the fan will
operate continuously during occupied periods. When set to 0 (Au-
tomatic), the fan will run only during a heating or cooling mode.
Remote Switch Config (RM.CF)
The remote switch input is connected to TB201 terminals 3 and 4.
This switch can be used for several remote control functions.
Please refer to the Remote Control Switch Input section for details
on its use and operation.
CEM Module Installed (CEM)
This configuration instructs the control to communicate with the
controls expansion module (CEM) over the local equipment net-
work (LEN) when set to Yes. When the unit is configured for cer-
tain sensors and configurations, this option will be set to Yes auto-
matically.
The sensors and configurations that automatically turn on this
board are:
Configuration
UNIT
SENS
SRH.S = Enable (Space Rela-
tive Humidity Sensor Enable)
Configuration
UNIT
SENS
RRH.S = Enable (Return Air
Relative Humidity Sensor Enable)
Configuration
EDT.R
RES.S = Enable (4 to 20 mA Supply
Air Reset Sensor Enable)
Configuration
ECON
ORH.S = Enable (Outside Air Relative
Humidity Sensor Enable)
Configuration
ECON
CFM.C
OCF.S = Enable (Outdoor
Air CFM Sensor Enable)
Configuration
DEHU
D.SEN = 3 (DISCR.INPUT) (Dehu-
midification Sensor – Discrete Input Select)
Configuration
DMD.L
DM.L.S = 1 (2 SWITCHES) (De-
mand Limiting using 2 discrete switches)
Configuration
DMD.L
DM.L.S = 2 (4-20 MA CTRL) (De-
mand Limiting using a 4 to 20 mA sensor)
Configuration
IAQ
AQ.CF
IQ.I.C = 1 (IAQ DISCRETE)
(IAQ discrete switch control)
Configuration
IAQ
AQ.CF
IQ.I.C = 2 (IAQ DISC.OVR)
(IAQ discrete switch “override” control)
Configuration
IAQ
AQ.CF
OQ.A.C = 1 (OAQ SENS-
DAQ) (Outdoor Air Quality Sensor)
Configuration
IAQ
AQ.CF
OQ.A.C = 2 (4-20 NO DAQ)
(4 to 20 mA sensor, no DAQ)
Configuration
SP
SP.RS = 1 (4-20 mA control) (static pres-
sure reset using 4-20 mA input)
Temperature Compensated Start Cooling Factor (TCS.C)
This factor is used in the equation of Temperature Compensated
Start Time Bias for cooling. Refer to the Temperature Compensat-
ed Start section for more information. A setting of 0 minutes indi-
cates Temperature Compensated Start in Cooling is not permitted.
Temperature Compensated Start Cooling Factor (TCS.H)
This factor is used in the equation of Temperature Compensated
Start Time Bias for heating. Refer to the Temperature Compensat-
ed Start section for more information. A setting of 0 minutes indi-
cates Temperature Compensated Start in Heating is not permitted.
Table 32 — Unit Configuration
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULTS
UNIT UNIT CONFIGURATION
C.TYP Machine Control Type 1 to 4 CTRLTYPE 4
SIZE Unit Size (30-100) 30 to 100 UNITSIZE 30
FN.MD Fan Mode (0=Auto, 1=Cont) 0 to 1 FAN_MODE 1
RM.CF Remote Switch Config 0 to 3 RMTINCFG 0
EM CEM Module Installed Yes/No CEM_BRD No
TCS.C Temp.Cmp.Strt.Cool Factr 0 to 60 min TCSTCOOL 0
TCS.H Temp.Cmp.Strt.Heat Factr 0 to 60 min TCSTHEAT 0
SFS.S Fan Fail Shuts Down Unit Yes/No SFS_SHUT No
SFS.M Fan Stat Monitoring Type 0 to 2 SFS_MON 0
VAV.S VAV Unocc.Fan Retry Time 0 to 720 min SAMPMINS 50
50.HZ 50 Hertz Unit? Yes/No UNIT_HZ No
MAT.S MAT Calc Config 0 to 2 MAT_SEL 1
MAT.R Reset MAT Table Entries? Yes/No MATRESET No
MAT.D MAT Outside Air Default 0 to 100 % MATOADOS 20
ALTI Altitude……..in feet: 0 to 60000 ALTITUDE 0
DLAY Startup Delay Time 0 to 900 sec DELAY 0
AUX.R Auxiliary Relay Config 0 to 3 AUXRELAY 0
SENS INPUT SENSOR CONFIG
D.183 Disable T183 Alert 0 to 1 1
SV.DH SAV Optimized for Dehumidification Yes/No
SPT.S Space Temp Sensor Enable/Disable SPTSENS Disable
SP.O.S Space Temp Offset Sensor Enable/Disable SPTOSENS Disable
SP.O.R Space Temp Offset Range 1 to 10 SPTO_RNG 5
SRH.S Space Air RH Sensor Enable/Disable SPRHSENS Disable
RRH.S Return Air RH Sensor Enable/Disable RARHSENS Disable
FLT.S Filter Stat.Sw.Enabled? Enable/Disable FLTS_ENA Disable