APPENDIX A — LOCAL DISPLAY TABLES
Table A — MODE — RUN STATUS
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS PAGE NO.
VIEW AUTO VIEW OF RUN STATUS
HVAC ascii string spelling out the hvac modes string 111,115
OCC Occupied ? YES/NO OCCUPIED forcible 111,115
MAT Mixed Air Temperature dF MAT 111,115
EDT Evaporator Discharge Tmp dF EDT 111,115
LAT Leaving Air Temperature dF LAT 111,115
EC.C.P Economizer Control Point dF ECONCPNT 77,87,111,115
ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS 111,115
EC2.P Economzr Act.Curr.Pos. 0-100 % ECON2POS 111,115
CL.C.P Cooling Control Point dF COOLCPNT 55,111,115
C.CAP Current Running Capacity CAPTOTAL 111,115
CL.ST Requested Cool Stage CL_STAGE 111,115
HT.C.P Heating Control Point dF HEATCPNT 64,111,115
HT.ST Requested Heat Stage HT_STAGE 65-67,111,115
H.MAX Maximum Heat Stages HTMAXSTG 65,111,115
ECON ECONOMIZER RUN STATUS
ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS 80,115,115
EC2.P Economzr 2 Act.Curr.Pos. 0-100 % ECON2POS 80,115,115
ECN.C Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible 80,115
ACTV Economizer Active ? YES/NO ECACTIVE 77,80,115
DISA ECON DISABLING CONDITIONS
DISAUNV.1 Econ Act. Unavailable? YES/NO ECONUNAV 80,115
DISAUNV.2 Econ2 Act. Unavailable? YES/NO ECN2UNAV 80,115
DISAENTH Enth. Switch Read High ? YES/NO ENTH 80,115
DISADBC DBC - OAT Lockout? YES/NO DBC_STAT 80,115
DISADEW DEW - OA Dewpt.Lockout? YES/NO DEW_STAT 80,115
DISADDBC DDBD- OAT > RAT Lockout? YES/NO DDBCSTAT 74,80,115
DISAOAEC OAEC- OA Enth Lockout? YES/NO OAECSTAT 80,115
DISA
DEC DEC - Diff.Enth.Lockout? YES/NO DEC_STAT 80,115
DISAEDT EDT Sensor Bad? YES/NO EDT_STAT 80,115
DISAOAT OAT Sensor Bad ? YES/NO OAT_STAT 80,115
DISAFORC Economizer Forced ? YES/NO ECONFORC 80,115
DISASFON Supply Fan Not On 30s ? YES/NO SFONSTAT 80,115
DISACLOF Cool Mode Not In Effect? YES/NO COOL_OFF 80,115
DISAOAQL OAQ Lockout in Effect ? YES/NO OAQLOCKD 80,115
DISAHELD Econ Recovery Hold Off? YES/NO ECONHELD 80,115
DISADH.DS Dehumid. Disabled Econ.? YES/NO DHDISABL 80,115
O.AIR OUTSIDE AIR INFORMATION 80,115
O.AIROAT Outside Air Temperature dF OAT forcible 80,115
O.AIROA.RH Outside Air Rel. Humidity % OARH forcible 80,115
O.AIROA.E Outside Air Enthalpy OAE 80,115
O.AIROA.D.T OutsideAir Dewpoint Temp dF OADEWTMP 80,115
COOL COOLING INFORMATION
C.CAP Current Running Capacity % CAPTOTAL 52,53,55,115,116
CUR.S Current Cool Stage COOL_STG 52,77,111,116
REQ.S Requested Cool Stage CL_STAGE 52,111,116
MAX.S Maximum Cool Stages CLMAXSTG 52,111,116
DEM.L Active Demand Limit % DEM_LIM forcible 52,53,111,116
SUMZ COOL CAP. STAGE CONTROL
SUMZSMZ Capacity Load Factor -100 +100 SMZ 52,111,116
SUMZADD.R Next Stage EDT Decrease ^F ADDRISE 52,53,116
SUMZ
SUB.R Next Stage EDT Increase ^F SUBRISE 52,53,116
SUMZR.PCT Rise Per Percent Capacity RISE_PCT 52,53,116
SUMZY.MIN Cap Deadband Subtracting Y_MINUS 52,53,116
SUMZY.PLU Cap Deadband Adding Y_PLUS 52,53,116
SUMZZ.MIN Cap Threshold Subtracting Z_MINUS 52,53,116
SUMZZ.PLU Cap Threshold Adding Z_PLUS 52,115
SUMZH.TMP High Temp Cap Override HI_TEMP 52,116
SUMZL.TMP Low Temp Cap Override LOW_TEMP 52,116
SUMZPULL Pull Down Cap Override PULLDOWN 52,116
SUMZSLOW Slow Change Cap Override SLO_CHNG 52,116,117
HMZR HUMIDIMIZER
HMZRCAPC HumidiMiZer Capacity HMZRCAPC 52,116
HMZRC.EXV Condenser EXV Position COND_EXV 52,116
HMZRB.EXV Bypass EXV Position BYP_EXV 52,116
HMZRRHV HumidiMiZer 3-way Valve HUM3WVAL 52,116
HMZRC.CPT Cooling Control Point COOLCPNT 52,116
HMZREDT Evaporator Discharge Tmp EDT 52,116
HMZRH.CPT Heating Control Point HEATCPNT 52,116
HMZRLAT Leaving Air Temperature LAT 52,116