APPENDIX B — CCN TABLES
All P Series units with ComtfortLink controls have a port for inter-
face with the Carrier Comfort Network
®
(CCN) system. On TB3,
there is a J11 jack which can be used for temporary connection to
the CCN network or to computers equipped with CCN software
like the Service Tool. Also on TB3, there are screw connections
that can be used for more permanent CCN connections.
In the following tables, the structure of the tables that are used
with the Service Tool as well as the names and data that are in-
cluded in each table are shown. There are several CCN variables
that are not displayed through the scrolling marquee and are
used for more extensive diagnostics and system evaluations.
Table L — STATUS DISPLAY TABLES
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
COOLING
HVAC Mode…………..: ascii text strings
Control Mode………..: ascii text strings
Current Running Capacity % CAPTOTAL
Total Capacity Needed % COOLCALC
Current Cool Stage COOL_STG
Requested Cool Stage CL_STAGE
Maximum Cool Stage CLMAXSTG
Cooling Control Point dF COOLCPNT
Evaporator Discharge Tmp dF EDT
Mixed Air Temperature dF MAT
Next capacity step down % CAPNXTDN
Next capacity step up % CAPNXTUP
COOL_A
Current Cool Stage COOL_STG
Cir A Discharge Pressure PSIG DP_A
Cir A Suction Pressure PSIG SP_A
Cir A Sat.Condensing Tmp dF SCTA
Cir A Sat.Suction Temp. dF SSTA
A1 Discharge Temperature dF DTA1
Suction Gas Temp Circ A dF RGTA
Compressor A1 Relay CMPA1
Compressor A2 Relay CMPA2
Compressor A3 Relay CMPA3
Compressor A1 Feedback CSB_A1
Compressor A2 Feedback CSB_A2
Compressor A3 Feedback CSB_A3
Circ A High Press.Switch CIRCAHPS
COOL_B
Current Cool Stage COOL_STG
Cir B Discharge Pressure DP_B
Cir B Suction Pressure PSIG SP_B
Cir B Sat.Condensing Tmp PSIG SCTB
Cir B Sat.Suction Temp. dF SSTB
Compressor B1 Relay CMPB1
Compressor B2 Relay CMPB2
Compressor B3 Relay CMPB3
Compressor B1 Feedback CSB_B1
Compressor B2 Feedback CSB_B2
Compressor B3 Feedback CSB_B3
Circ B High Press.Switch CIRCBHPS
ECONDIAG
Economizer Active ? Yes/No ECACTIVE
Conditions which prevent
Economizer being active:
Econ Act. Unavailable? Yes/No ECONUNAV
Econ2 Act. Unavailable Yes/No ECN2UNAV
Enth.Switch Read High ? Yes/No ENTH
DBC - OAT lockout? Yes/No DBC_STAT
DEW - OA Dewpt. lockout? Yes/No DEW_STAT
DDBC- OAT > RAT lockout? Yes/No DDBCSTAT
OAEC- OA Enth Lockout? Yes/No OAECSTAT
DEC - Diff.Enth.Lockout? Yes/No DEC_STAT
EDT Sensor Bad ? Yes/No EDT_STAT
OAT Sensor Bad ? Yes/No OAT_STAT
Economizer forced ? Yes/No ECONFORC
Supply Fan not on 30s ? Yes/No SFONSTAT
Cool Mode not in effect? Yes/No COOL_OFF
OAQ lockout in effect ? Yes/No OAQLOCKD
Econ recovery hold off? Yes/No ECONHELD
Dehumid. Disabled Econ.? Yes/No DHDISABL