190
CCN CCN CONFIGURATION
CCNA CCN Address 1 to 239 CCNADD 1 93
CCNB CCN Bus Number 0 to 239 CCNBUS 0 93
BAUD CCN Baud Rate 1 to 5 (multi-text strings) CCNBAUDD 3 93
BROD CCN BROADCST DEFINITIONS
BRODTM.DT CCN Time/Date Broadcast ON/OFF CCNBC On 93
BRODOAT.B CCN OAT Broadcast ON/OFF OATBC Off 93
BRODORH.B CCN OARH Broadcast ON/OFF OARHBC Off 93
BRODOAQ.B CCN OAQ Broadcast ON/OFF OAQBC Off 93, 94
BRODG.S.B Global Schedule Broadcst ON/OFF GSBC Off 93, 94
BRODB.ACK CCN Broadcast Ack'er ON/OFF CCNBCACK Off 93, 94
SC.OV CCN SCHEDULES-OVERRIDES
SC.OVSCH.N Schedule Number 0 to 99 SCHEDNUM 1 33, 35, 93, 94
SC.OVHOL.T Accept Global Holidays? YES/NO HOLIDAYT No 93, 94
SC.OVO.T.L. Override Time Limit 0 to 4 HRS OTL 1 93, 94
SC.OVOV.EX Timed Override Hours 0 to 4 HRS OVR_EXT 0 93, 94
SC.OVSPT.O SPT Override Enabled ? YES/NO SPT_OVER Yes 93, 94
SC.OVT58.O T58 Override Enabled ? YES/NO T58_OVER Yes 93, 94
SC.OVGL.OV Global Sched. Override ? YES/NO GLBLOVER No 93, 94
ALLM ALERT LIMIT CONFIG.
SP.L.O SPT lo alert limit/occ -10-245 dF SPLO 60 94
SP.H.O SPT hi alert limit/occ -10-245 dF SPHO 85 94
SP.L.U SPT lo alert limit/unocc -10-245 dF SPLU 45 94
SP.H.U SPT hi alert limit/unocc -10-245 dF SPHU 100 94
SA.L.O EDT lo alert limit/occ -40-245 dF SALO 40 94, 95
SA.H.O
EDT hi alert limit/occ -40-245 dF SAHO 100 94, 95
SA.L.U EDT lo alert limit/unocc -40-245 dF SALU 40 94, 95
SA.H.U EDT hi alert limit/unocc -40-245 dF SAHU 100 94, 95
RA.L.O RAT lo alert limit/occ -40-245 dF RALO 60 94, 95
RA.H.O RAT hi alert limit/occ -40-245 dF RAHO 90 94, 95
RA.L.U RAT lo alert limit/unocc -40-245 dF RALU 40 94, 95
RA.H.U RAT hi alert limit/unocc -40-245 dF RAHU 100 94, 95
OAT.L OAT lo alert limit -40-245 dF OATL -40 94, 95
OAT.H OAT hi alert limit -40-245 dF OATH 150 94, 95
R.RH.L RARH low alert limit 0-100 % RRHL 0 94, 95
R.RH.H RARH high alert limit 0-100 % RRHH 100 94, 95
O.RH.L OARH low alert limit 0-100 % ORHL 0 94, 95
O.RH.H OARH high alert limit 0-100 % ORHH 100 94, 95
SP.L SP low alert limit 0-5 " H2O SPL 0 94, 95
SP.H SP high alert limit 0-5 " H2O SPH 2 94, 95
BP.L BP lo alert limit -0.25-0.25 " H2O BPL -0.25 94, 95
BP.H BP high alert limit -0.25-0.25 " H2O BPH 0.25 94, 95
IAQ.H IAQ high alert limit 0-5000 IAQH 1200 94, 95
TRIM SENSOR TRIM CONFIG.
SAT.T Air Temp Lvg SF Trim -10 to 10 ^F SAT_TRIM 0 95, 96
RAT.T RAT Trim -10 to 10 ^F RAT_TRIM 0 95, 96
OAT.T OAT Trim -10 to 10 ^F OAT_TRIM 0 95, 96
SPT.T SPT Trim -10 to 10 ^F SPT_TRIM 0 95, 96
L.SW.T Limit Switch Trim -10 to 10 ^F LSW_TRIM 0 96
CCT.T Air Temp Lvg Evap Trim -10 to 10 ^F CCT_TRIM 0 96
DTA.1 A1 Discharge Temp Trim -10 to 10 ^F DTA1TRIM 0 96
SP.A.T Suct.Press.Circ.A Trim -50 to 50 PSIG SPA_TRIM 0 96
SP.B.T Suct.Press.Circ.B Trim -50 to 50 PSIG SPB_TRIM 0 96
DP.A.T Dis.Press.Circ.A Trim -50 to 50 PSIG DPA_TRIM 0 96
DP.B.T Dis.Press.Circ.B Trim -50 to 50 PSIG DPB_TRIM 0 96
SW.LG SWITCH LOGIC: NO / NC
FTS.L Filter Status Inpt-Clean Open/Close FLTSLOGC Open 96, 97
IGC.L IGC Feedback - Off Open/Close GASFANLG Open 96, 97
RMI.L RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open 96, 97
ENT.L Enthalpy Input - Low Open/Close ENTHLOGC Close 96, 97
SFS.L Fan Status Sw. - Off Open/Close SFSLOGIC Open 96, 97
DL1.L Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open 96, 97
DL2.L Dmd.Lmt.Sw.2 - Off Open/Close DMD_SW2L Open 96, 97
IAQ.L IAQ Disc.Input - Low Open/Close IAQINLOG Open 96, 97
FSD.L Fire Shutdown - Off Open/Close FSDLOGIC Open 96, 97
PRS.L Pressurization Sw. - Off Open/Close PRESLOGC Open 96, 97
EVC.L Evacuation Sw. - Off Open/Close EVACLOGC Open 97
PRG.L Smoke Purge Sw. - Off Open/Close PURGLOGC Open 97
DH.LG Dehumidify Sw. - Off Open/Close DHDISCLG Open 97
DISP DISPLAY CONFIGURATION
TEST Test Display LEDs ON/OFF TEST Off 97, 98
METR Metric Display ON/OFF DISPUNIT Off 97, 98
LANG Language Selection 0 to 1 (multi-text strings) LANGUAGE 0 97, 98
PAS.E Password Enable ENABLE/DISABLE PASS_EBL Enable 97, 98
PASS Service Password 0000 to 9999 PASSWORD 1111 97, 98
APPENDIX A — LOCAL DISPLAY TABLES
Table H — MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.