197
Table M — SET POINT TABLE
VFD_DATA (cont) VFD1 DI4 State Open/Close VFD1_DI4
VFD1 DI5 State Open/Close VFD1_DI5
VFD1 DI6 State Open/Close VFD1_DI6
VFD1 AI1 (% of range) % VFD1_AI1
VFD1 AI2 (% of range) % VFD1_AI2
VFD2 Status Word 1 VFD2STAT
VFD2 Actual Speed % VFD2_SPD
VFD2 Actual Motor RPM VFD2RPM
VFD2 Actual Motor Freq VFD2FREQ
VFD2 Actual Motor Amps amps VFD2AMPS
VFD2 Actual Motor Torque % VFD2TORQ
VFD2 Actual Motor Power VFD2PWR
VFD2 DC Bus Voltage volts VFD2VDC
VFD2 Output Voltage volts VFD2VOUT
VFD2 Transistor Temp (C) VFD2TEMP
VFD2 Cumulative Run Time hours VFD2RUNT
VFD2 Cumulative kWh VFD2KWH
VFD2 Last Fault Code VFD2LFC
VFD2 DI1 State Open/Close VFD2_DI1
VFD2 DI2 State Open/Close VFD2_DI2
VFD2 DI3 State Open/Close VFD2_DI3
VFD2 DI4 State Open/Close VFD2_DI4
VFD2 DI5 State Open/Close VFD2_DI5
VFD2 DI6 State Open/Close VFD2_DI6
VFD2 AI1 (% of range) % VFD2_AI1
VFD2 AI2 (% of range) % VFD2_AI2
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
SET_PNT
Occupied Heat Setpoint 40-99 dF OHSP 68
Occupied Cool Setpoint 40-99 dF OCSP 75
Unoccupied Heat Setpoint 40-99 dF UHSP 55
Unoccupied Cool Setpoint 40-110 dF UCSP 90
Heat-Cool Setpoint Gap 2-10 deltaF HCSP_GAP 5
VAV Occ. Cool On Delta 0-25 deltaF VAVOCON 3.5
VAV Occ. Cool Off Delta 1-25 deltaF VAVOCOFF 2
Supply Air Setpoint 45-75 dF SASP 55
Supply Air Setpoint Hi 45-75 dF SASP_HI 55
Supply Air Setpoint Lo 45-75 dF SASP_LO 60
Heating Supply Air Setpt 90-145 dF SASPHEAT 85
Tempering Purge SASP -20-80 dF TEMPPURG 50
Tempering in Cool SASP 5-75 dF TEMPCOOL 5
Tempering in Vent Occ SASP -20-80 dF TEMPVOCC 65
Tempering Vent Unocc. SASP -20-80 dF TEMPVUNC 50
APPENDIX B — CCN TABLES
Table L — STATUS DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS