204
TRIM
Air Temp Lvg SF Trim -10 to 10 ^F SAT_TRIM 0
RAT Trim -10 to 10 ^F RAT_TRIM 0
OAT Trim -10 to 10 ^F OAT_TRIM 0
SPT Trim -10 to 10 ^F SPT_TRIM 0
Limit Switch Trim -10 to 10 ^F LSW_TRIM 0
Air Temp Lvg Evap Trim -10 to 10 ^F CCT_TRIM 0
A1 Discharge Temp Trim -10 to 10 ^F DTA1TRIM
Suction Gas Temp A Trim -10 to 10 ^F RGTATRIM
Suct.Press.Circ.A Trim -50 to 50 SPA_TRIM 0
Suct.Press.Circ.B Trim -50 to 50 SPB_TRIM 0
Dis.Press.Circ.A Trim -50 to 50 DPA_TRIM 0
Dis.Press.Circ.B Trim -50 to 50 DPB_TRIM 0
Static Press. Trim (ma) -2 to 2 SPMATRIM 0
Bldg. Pressure Trim (ma) -2 to 2 BPMATRIM 0
Outside Air CFM Trim (ma) -2 to 2 OAMATRIM 0
Supply Air CFM Trim (ma) -2 to 2 SAMATRIM 0
Return Air CFM (ma) -2 to 2 RAMATRIM 0
UNIT
Machine Control Type 1-6 CTRLTYPE 4
Unit Size (30-100) 30-100 UNITSIZE 30
Fan Mode (0=auto, 1=cont) 0-1 FAN_MODE 1
Remote Switch Config 0 to 3 RMTINCFG 0
CEM Module Installed Yes/No CEM_BRD No
Temp.Cmp.Strt.Cool Factr 0-60 min TCSTCOOL 0
Temp.Cmp.Strt.Heat Factr 0-60 min TCSTHEAT 0
Fan fail shuts down unit Yes/No SFS_SHUT No
Fan Stat Monitoring Type 0-2 SFS_MON 0
VAV Unocc.Fan Retry time 0-720 min SAMPMINS 50
50 Hertz Unit ? Yes/No UNIT_HZ No
MAT Calc Config Type 0-2 MAT_SEL 1
Reset MAT Table Entries? Yes/No MATRESET No
MAT Outside Air Default 0 to 100 % MATOAPOS 20
Altitude……..in feet: 0-60000 ALTITUDE 0
MAT Outside Air Default % MATOAPOS
Startup Delay Time 0 to 900 secs DELAY 0
Auxiliary Relay Config 0 to 3 (multi-text strings) AUXRELAY 0
Space Temp Sensor Enable/Disable SPTSENS Disable
Space Temp Offset Sensor Enable/Disable SPTOSENS Disable
Space Temp Offset Range 1 to 10 SPTO_RNG 5
Space Air RH Sensor Enable/Disable SPRHSENS Disable
Return Air RH Sensor Enable/Disable RARHSENS Disable
Filter Stat.Sw.Enabled ? Enable/Disable FLTS_ENA Disable
APPENDIX B — CCN TABLES
Table O — SERVICE-CONFIG TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT