APPENDIX D — VFD INFORMATION
Table AB — VFD Parameters Configured by Carrier Assistant
* 41 for Supply Fan Motor VFD, 42 for Exhaust Fan Motor VFD.
Table AC — VFD Parameters with CCN Points Configured with ComfortLink Controls
Table AD — VFD Parameters Configured with ComfortLink Controls
PARAMETER GROUP PARAMETER TITLE PARAMETER INDEX HVAC DEFAULT CARRIER DEFAULT
Options COMM PROT SEL 9802 NOT SEL (0) LEN (6)
EFB Protocol
EFB PROTOCOL ID 5301 0000 hex 0601 hex
EFB STATION ID 5302 0 41/42*
EFB BAUD RATE 5303 9.6 kb/s 38.4 kb/s
EFB PARITY 5304 8 NONE 1 8 NONE 1
EFB CTRL PROFILE 5305 ABB DRV LIM DCU PROFILE
PARAMETER
GROUP
PARAMETER TITLE
PARAMETER
INDEX
HVAC DEFAULT
CARRIER
DEFAULT
CCN POINT
SUPPLY FAN VFD
CCN POINT
EXHAUST FAN
VFD
Start-Up Data
MOTOR NOM VOLT 9905
230V,460V,575V
Refer to motor
nameplate
VFD1NVLT VFD2NVLT
MOTOR NOM
CURR
9906
1.0 In
Refer to motor
nameplate
VFD1NAMP VFD2NAMP
MOTOR NOM FREQ 9907
60 Hz 60 Hz VFD1NFRQ VFD2NFRQ
MOTOR NOM
SPEED
9908
1750 rpm 1750 rpm VFD1NRPM VFD2NRPM
MOTOR NOM
POWER
9909
1.0 Pn
Refer to motor
nameplate
VFD1NPWR VFD2NPWR
Start/Stop/Dir DIRECTION 1003 FORWARD REQUEST VFD1MDIR VFD2MDIR
Accel/Decel
ACCELER TIME 1 2202 30.0s 30.0s VFD1ACCL VFD2ACCL
DECELER TIME 1 2203 30.0s 30.0s VFD1DECL VFD2DECL
Motor Control SWITCHING FREQ 2606 4 kHz 8 kHz VFD1SWFQ VFD2SWFQ
PARAMETER GROUP PARAMETER TITLE PARAMETER INDEX HVAC DEFAULT CARRIER DEFAULT
Start/Stop/Dir EXT1 COMMANDS 1001 DI1 COMM (10)
Reference Select REF1 SELECT 1103 AI1 COMM (8)
Constant Speeds
CONST SPEED SEL 1201 DI3 NOT SEL (0)
CONST SPEED 7 1208 60 Hz 0 Hz
System Controls
RUN ENABLE 1601 NOT SEL NOT SEL (0)
FAULT RESET SEL 1604 KEYPAD COMM (8)
START ENABLE 1 1608 DI4 DI4 (4)
Start/Stop
START FUNCTION 2101 SCALAR FLYSTART AUTO (1)
STOP FUNCTION 2102 COAST RAMP (2)
Fault Functions
COMM FAULT FUNC 3018 NOT SEL CONST SP 7 (2)
COMM FAULT TIME 3019 10.0 s 10.0 s
Automatic Reset
AR OVERCURRENT 3104 Disable (0) Disable (0)
AR OVERVOLTAGE 3105 Enable (1) Disable (0)
AR UNDERVOLTAGE 3106 Enable (1) Disable (0)
AR AI<MIN 3107 Enable (1) Disable (0)
AR EXTERNAL FAULT 3108 Enable (1) Disable (0)