Demand Limit In Effect MODEDMLT R 0 to 1 BV:31 modedmlt_1
Demand Limit Sw.1 Setpt. DLSWSP1 W % 80 0 to 100 AV:53 dlswsp1_1
Demand Limit Sw.2 Setpt. DLSWSP2 W % 50 0 to 100 AV:54 dlswsp2_1
Demand Limit Switch 1 DMD_SW1 W 0 to 1 BV:1006 dmd_sw1_1
Demand Limit Switch 2 DMD_SW2 W 0 to 1 BV:1007 dmd_sw2_1
DEW - OA Dewpt.Lockout? DEW_STAT R 0 to 1 BV:32 dew_stat_1
Diff.Air Quality in PPM DAQ R 0 to 5000 AV:56 daq_1
Dmd Level Low Cool ON DMDLCON W ^F 1.5 0 to 2 AV:63 dmdlcon_1
Dmd Level Low Heat ON DMDLHON W ^F 1.5 0 to 2 AV:64 dmdlhon_1
Dmd Level(-) Low Cool OFF DMDLCOFF W ^F 1 0.5 to 2 AV:59 dmdlcoff_1
Dmd Level(-) Low Heat OFF DMDLHOFF W ^F 1 0.5 to 2 AV:60 dmdlhoff_1
Dmd Level(+) Hi Cool ON DMDHCON W ^F 0.5 0.5 to 20 AV:61 dmdhcon_1
Dmd Level(+) Hi Heat ON DMDHHON W ^F 0.5 0.5 to 20 AV:62 dmdhhon_1
Econ Act. Unavailable? ECONUNAV R 0 to 1 BV:34 econunav_1
Econ Command Position ECN2CPOS W % 0 to 100 AV:41 ecn2cpos_1
Econ disable in DH mode? DHECDISA W Yes 0 to 1 BV:35 dhecdisa_1
Econ Recovery Hold Off? ECONHELD R 0 to 1 BV:42 econheld_1
Econo Current Min. CFM ECMINCFM R CFM 0 to 20000 AV:42 ecmincfm_1
Econo Current Min. Pos. ECMINPOS R % 0 to 100 AV:45 ecminpos_1
Economizer Act. Curr. Pos ECONOPOS R % 0 to 100 AV:1028 econ_pos_1
Economizer Act.Cmd Pos ECONOCMD W % 0 to 100 AV:67 econocmd_1
Economizer Active? ECACTIVE R 0 to 1 BV:36 ecactive_1
Economizer Control Point ECONCPNT R dF 0 to 180 AV:68 econpnt_1
Economizer Forced ? ECONFORC R 0 to 1 BV:38 econforc_1
Economizer Max.Position ECONOMAX W % 98 0 to 100 AV:70 economax_1
Economizer Min.Flow OACFMMAX W CFM 2000 0 to 20000 AV:46 oacfmmax_1
Economizer Min.Position ECONOMIN W % 5 0 to 100 AV:4005 econ_min_1
EDT Sensor Bad ? EDT_STAT R 0 to 1 BV:44 edt_stat_1
Element Comm Status R BV:2999 element_stat_1
Element Communications Alarm R BV:105 comm_lost_alm_1
Emergency Stop EMSTOP W 0 to 1 BV:45 emstop_1
Enth. Switch Read High ? ENTH W 0 to 1 BV:40 enth_1
Equipment Alarm R BV:127 element_alarm_1
Evacuation Input EVAC W 0 to 1 BV:1060 smk_evac_1
Evaporator Discharge Tmp EDT R dF -40 to 240 AV:76 edt_1
Exhaust Fan VFD Speed EFAN_VFD R % 0 to 100 AV:2075 ef_vfd_output_1
Fan Fail Shuts Down Unit SFS_SHUT W No 0 to 1 BV:50 sfs_shut_1
Fan Mode FAN_MODE W 1 0 to 1 AV:77 fan_mode_1
Fan request from IGC IGCFAN R 0 to 1 BV:11 igcfan_1
Fan Track Control D.CFM DELTACFM R CFM
–20000
to 20000 AV:47 deltacfm_1
Fan Track Internal RAM DCFM_RAM W CFM 0
–20000
to 20000 AV:48 dcfm_ram_1
Fan Track Max Clamp DCFM_MAX W CFM 4000 0 to 20000 AV:51 dcfm_max_1
Fan Track Max Correction DCFM_ADJ W CFM 1000 0 to 20000 AV:52 dcfm_adj_1
Filter Status Input FLTS W 0 to 1 BV:1052 filter_status_1
Fire Shutdown Input FSD W 0 to 1 BV:1005 firedown_status_1
Freeze Status Switch FRZ W 0 to 1 BV:41 frz_1
Heat Interlock Relay HIR W 0 to 1 BV:1026 heat_interlock_relay_1
Heat Relay 1 HS1 R 0 to 1 BV:52 hs1_1
Heat Relay 2
HS2 R 0 to 1 BV:53 hs2_1
Heat-Cool Setpoint Gap HCSP_GAP W deltaF 2 to 10 AV:83 hcsp_gap_1
Heating Control Point HEATCPNT R –20 to 140 AV:1025 heat_ctrl_point_1
Heating Occupied Setpoint OHSP W dF 40 to 99 AV:3002 occ_ht_stpt_1
Heating Supply Air Setpt SASPHEAT W dF 85 80 to 120 AV:85 saspheat_1
Heating Unoccupied Setpoint UHSP W dF 40 to 99 AV:3004 unocc_ht_stpt_1
Hi Limit Switch Tmp Mode LIMTMODE R 0 to 1 BV:55 limtmode_1
High OAT Lockout Temp OAT_LOCK W dF 60 –40 to 120 AV:9008 econ_oat_lockout_1
Ht.Coil Command Position HTCLCPOS R % 0 to 100 AV:55 htclcpos_1
Humidifier Relay HUMIDRLY R 0 to 1 BV:46 humidrly_1
HumidiMiZer 3-way Valve HUM3WVAL R 0 to 1 BV:47 hum3wval_1
HumidiMiZer Capacity HMZRCAPC R % 0 to 100 AV:57 hmzrcapc_1
HVAC Mode Numerical Form MODEHVAC R 0 to 40 AV:1022 hvac_mode_1
IAQ - Discrete Input IAQIN W 0 to 1 BV:1050 iaq_status_1
IAQ - PPM Indoor CO2 IAQ W 0 to 5000 AV:1009 iaq_1
IAQ Demand Vent Min.Flow OACFMMIN W CFM 0 0 to 20000 AV:58 oacfmmin_1
IAQ Pre-Occ Purge Active MODEIQPG R 0 to 1 BV:56 modeiqpg_1
IAQ Purge Duration IAQPTIME W min 15 5 to 60 AV:98 iaqptime_1
IAQ Purge OAT Lockout IAQPNTLO W dF 50 35 to 70 AV:101 iaqpntlo_1
LAT Cutoff Mode LATCMODE R 0 to 1 BV:58 latcmode_1
Leaving Air Temperature LAT R dF –40 to 240 AV:1027 lvg_air_temperature_1
Local Machine Disable UNITSTOP W 0 to 1 BV:59 unitstop_1
Local Schedule R n/a BV:5 schedule_1
Low Temp Cap Override LOW_TEMP R 0 to 1 BV:61 low_temp_1
Mech Cooling Locked Out MODELOCK R 0 to 1 BV:63 modelock_1
APPENDIX F — UPC OPEN CONTROLLER
Table AP — NETWORK POINTS LIST (cont)
POINT DESCRIPTION
CCN POINT
NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET OBJECT
NAME

Table of Contents