236
LEGEND
Temp Comp Start Cool Factor TCSTCOOL W min 0 0 to 60 AV:159 tcstcool_1
Temp Comp Start Heat Factor TCSTHEAT W min 0 0 to 60 AV:160 tcstheat_1
Temp Compensated Start MODETCST R 0 to 1 BV:96 modetcst_1
Temper Supply Air Setpt SASPTEMP W dF 35 to 70 AV:15 sasptemp_1
Temper Vent Unocc TEMPVUNC W dF –20 to 80 AV:164 tempvunc_1
Tempering in Cool SASP TEMPCOOL W dF 5 to 75 AV:161 tempcool_1
Tempering Purge SASP TEMPPURG W dF –20 to 80 AV:162 temppurg_1
Tempering Vent Occ SASP TEMPVOCC W dF –20 to 80 AV:163 tempvocc_1
Thermostat G Input G W 0 to 1 BV:1021 g_input_1
Thermostat W1 Input W1 W 0 to 1 BV:1019 w1_input_1
Thermostat W2 Input W2 W 0 to 1 BV:1020 w2_input_1
Thermostat Y1 Input Y1 W 0 to 1 BV:1017 y1_input_1
Thermostat Y2 Input Y2 W 0 to 1 BV:1018 y2_input_1
Timed Override In Effect MODETOVR R 0 to 1 BV:97 modetovr_1
Timed-Override in Effect OVERLAST R 0 to 1 BV:98 overlast_1
Un.Ec.Free Cool OAT Lock UEFCNTLO W dF 50 40 to 70 AV:166 uefcntlo_1
Unoc Econ Free Cool Cfg UEFC_CFG W 0 0 to 2 AV:172 uefc_cfg_1
Unoc Econ Free Cool Time UEFCTIME W min 120 0 to 720 AV:173 uefctime_1
Unoccupied Cool Mode End UCCL_END R 0 to 100 AV:168 uccl_end_1
Unoccupied Cool Mode Start UCCLSTRT R 0 to 100 AV:169 ucclstrt_1
Unoccupied Heat Mode End UCHT_END R 0 to 100 AV:170 ucht_end_1
Unoccupied Heat Mode Start UCHTSTRT R 0 to 100 AV:171 uchtstrt_1
User Defined Analog 1 W AV:2901 user_analog_1_1
User Defined Analog 2 W AV:2902 user_analog_2_1
User Defined Analog 3 W AV:2903 user_analog_3_1
User Defined Analog 4 W AV:2904 user_analog_4_1
User Defined Analog 5 W AV:2905 user_analog_5_1
User Defined Binary 1 W BV:2911 user_binary_1_1
User Defined Binary 2 W BV:2912 user_binary_2_1
User Defined Binary 3 W BV:2913 user_binary_3_1
User Defined Binary 4 W BV:2914 user_binary_4_1
User Defined Binary 5 W BV:2915 user_binary_5_1
VAV Occ. Cool Off Delta VAVOCOFF W deltaF 1 to 25 AV:180 vavocoff_1
VAV Occ. Cool On Delta VAVOCON W deltaF 0 to 25 AV:181 vavocon_1
Vent Reheat RAT Offset DHVRAOFF W ^F 0 0 to 8 AV:183 dhvraoff_1
Vent Reheat Setpoint DHVHT_SP W dF 70 55 to 95 AV:184 dhvht_sp_1
VFD Maximum Speed STATPMAX W % 100 0 to 100 AV:188 statpmax_1
VFD Minimum Speed STATPMIN W % 20 0 to 100 AV:189 statpmin_1
VFD/Act. Fire Speed/Pos. BLDGPFSO W % 100 0 to 100 AV:186 bldgpfso_1
VFD/Act. Min. Speed/Pos. BLDGPMIN W % 0 0 to 100 AV:105 bldgpmin_1
VFD1 Actual Motor Amps VFD1AMPS R A 0 to 999 AV:79 vfd1amps_1
VFD1 Actual Motor Freq VFD1FREQ R 0 to 500 AV:80 vfd1freq_1
VFD1 Actual Motor Power VFD1PWR R –150 to 150 AV:81 vfd1pwr_1
VFD1 Actual Motor RPM VFD1RPM R 0 to 30000 AV:82 vfd1rpm_1
VFD1 Cumulative kWh VFD1KWH R 0 to 65535 AV:84 vfd1kwh_1
VFD1 Cumulative Run Time VFD1RUNT R hr 0 to 65535 AV:86 vfd1runt_1
VFD1 DC Bus Voltage VFD1VDC R V 0 to 1000 AV:87 vfd1vdc_1
VFD1 Last Fault Code VFD1LFC R 0 to 65535 AV:88 vfd1lfc_1
VFD1 Output Voltage VFD1VOUT R V 0 to 1000 AV:89 vfd1vout_1
VFD1 Status Word 1 VFD1STAT R 0 to 0 AV:90 vfd1stat_1
VFD1 Transistor Temp (C) VFD1TEMP R 0 to 150 AV:91 vfd1temp_1
VFD2 Actual Motor Amps VFD2AMPS R A 0 to 999 AV:92 vfd2amps_1
VFD2 Actual Motor Freq VFD2FREQ R 10 to 500 AV:93 vfd2freq_1
VFD2 Actual Motor Power VFD2PWR R –150 to 150 AV:94 vfd2pwr_1
VFD2 Actual Motor RPM VFD2RPM R 50 to 30000 AV:95 vfd2rpm_1
VFD2 Cumulative kWh VFD2KWH R 0 to 65535 AV:96 vfd2kwh_1
VFD2 Cumulative Run Time VFD2RUNT R hr 0 to 65535 AV:97 vfd2runt_1
VFD2 DC Bus Voltage VFD2VDC R V 0 to 1000 AV:99 vfd2vdc_1
VFD2 Last Fault Code VFD2LFC R 0 to 65535 AV:100 vfd2lfc_1
VFD2 Output Voltage VFD2VOUT R V 0 to 1000 AV:102 vfd2vout_1
VFD2 Status Word 1 VFD2STAT R 0 to 0 AV:103 vfd2stat_1
VFD2 Transistor Temp (C) VFD2TEMP R 0 to 150 AV:104 vfd2temp_1
VFD-IGV Fire Speed Override STATPFSO W % 100 0 to 100 AV:187 statpfso_1
APPENDIX F — UPC OPEN CONTROLLER
Table AP — NETWORK POINTS LIST (cont)
POINT DESCRIPTION
CCN POINT
NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET OBJECT
NAME
BP — Building Pressure OAEC — Outdoor Air Enthalpy Changeover
DBC — Dry Bulb Changeover OAQ — Outdoor Air Quality
DCV — Demand Controlled Ventilation OAT — Outdoor Air Temperature
DDBC — Differential Dry Bulb Changeover R—Read
DEC — Differential Enthalpy Changeover RAT — Return Air Temperature
EDT — Evaporator Discharge Temperature RH — Relative Humidity
EXV — Electronic Expansion Valve SASP — Supply Air Set Point
IAQ — Indoor Air Quality SPT — Space Temperature
IGV — Inlet Guide Vanes VAV — Variable Air Volume
LAT — Leaving Air Temperature VFD — Variable Frequency Drive
n/a — Not Available W—Write