LEGEND
Temp Comp Start Cool Factor TCSTCOOL W min 0 0 to 60 AV:159 tcstcool_1
Temp Comp Start Heat Factor TCSTHEAT W min 0 0 to 60 AV:160 tcstheat_1
Temp Compensated Start MODETCST R 0 to 1 BV:96 modetcst_1
Temper Supply Air Setpt SASPTEMP W dF 35 to 70 AV:15 sasptemp_1
Temper Vent Unocc TEMPVUNC W dF –20 to 80 AV:164 tempvunc_1
Tempering in Cool SASP TEMPCOOL W dF 5 to 75 AV:161 tempcool_1
Tempering Purge SASP TEMPPURG W dF –20 to 80 AV:162 temppurg_1
Tempering Vent Occ SASP TEMPVOCC W dF –20 to 80 AV:163 tempvocc_1
Thermostat G Input G W 0 to 1 BV:1021 g_input_1
Thermostat W1 Input W1 W 0 to 1 BV:1019 w1_input_1
Thermostat W2 Input W2 W 0 to 1 BV:1020 w2_input_1
Thermostat Y1 Input Y1 W 0 to 1 BV:1017 y1_input_1
Thermostat Y2 Input Y2 W 0 to 1 BV:1018 y2_input_1
Timed Override In Effect MODETOVR R 0 to 1 BV:97 modetovr_1
Timed-Override in Effect OVERLAST R 0 to 1 BV:98 overlast_1
Un.Ec.Free Cool OAT Lock UEFCNTLO W dF 50 40 to 70 AV:166 uefcntlo_1
Unoc Econ Free Cool Cfg UEFC_CFG W 0 0 to 2 AV:172 uefc_cfg_1
Unoc Econ Free Cool Time UEFCTIME W min 120 0 to 720 AV:173 uefctime_1
Unoccupied Cool Mode End UCCL_END R 0 to 100 AV:168 uccl_end_1
Unoccupied Cool Mode Start UCCLSTRT R 0 to 100 AV:169 ucclstrt_1
Unoccupied Heat Mode End UCHT_END R 0 to 100 AV:170 ucht_end_1
Unoccupied Heat Mode Start UCHTSTRT R 0 to 100 AV:171 uchtstrt_1
User Defined Analog 1 W AV:2901 user_analog_1_1
User Defined Analog 2 W AV:2902 user_analog_2_1
User Defined Analog 3 W AV:2903 user_analog_3_1
User Defined Analog 4 W AV:2904 user_analog_4_1
User Defined Analog 5 W AV:2905 user_analog_5_1
User Defined Binary 1 W BV:2911 user_binary_1_1
User Defined Binary 2 W BV:2912 user_binary_2_1
User Defined Binary 3 W BV:2913 user_binary_3_1
User Defined Binary 4 W BV:2914 user_binary_4_1
User Defined Binary 5 W BV:2915 user_binary_5_1
VAV Occ. Cool Off Delta VAVOCOFF W deltaF 1 to 25 AV:180 vavocoff_1
VAV Occ. Cool On Delta VAVOCON W deltaF 0 to 25 AV:181 vavocon_1
Vent Reheat RAT Offset DHVRAOFF W ^F 0 0 to 8 AV:183 dhvraoff_1
Vent Reheat Setpoint DHVHT_SP W dF 70 55 to 95 AV:184 dhvht_sp_1
VFD Maximum Speed STATPMAX W % 100 0 to 100 AV:188 statpmax_1
VFD Minimum Speed STATPMIN W % 20 0 to 100 AV:189 statpmin_1
VFD/Act. Fire Speed/Pos. BLDGPFSO W % 100 0 to 100 AV:186 bldgpfso_1
VFD/Act. Min. Speed/Pos. BLDGPMIN W % 0 0 to 100 AV:105 bldgpmin_1
VFD1 Actual Motor Amps VFD1AMPS R A 0 to 999 AV:79 vfd1amps_1
VFD1 Actual Motor Freq VFD1FREQ R 0 to 500 AV:80 vfd1freq_1
VFD1 Actual Motor Power VFD1PWR R –150 to 150 AV:81 vfd1pwr_1
VFD1 Actual Motor RPM VFD1RPM R 0 to 30000 AV:82 vfd1rpm_1
VFD1 Cumulative kWh VFD1KWH R 0 to 65535 AV:84 vfd1kwh_1
VFD1 Cumulative Run Time VFD1RUNT R hr 0 to 65535 AV:86 vfd1runt_1
VFD1 DC Bus Voltage VFD1VDC R V 0 to 1000 AV:87 vfd1vdc_1
VFD1 Last Fault Code VFD1LFC R 0 to 65535 AV:88 vfd1lfc_1
VFD1 Output Voltage VFD1VOUT R V 0 to 1000 AV:89 vfd1vout_1
VFD1 Status Word 1 VFD1STAT R 0 to 0 AV:90 vfd1stat_1
VFD1 Transistor Temp (C) VFD1TEMP R 0 to 150 AV:91 vfd1temp_1
VFD2 Actual Motor Amps VFD2AMPS R A 0 to 999 AV:92 vfd2amps_1
VFD2 Actual Motor Freq VFD2FREQ R 10 to 500 AV:93 vfd2freq_1
VFD2 Actual Motor Power VFD2PWR R –150 to 150 AV:94 vfd2pwr_1
VFD2 Actual Motor RPM VFD2RPM R 50 to 30000 AV:95 vfd2rpm_1
VFD2 Cumulative kWh VFD2KWH R 0 to 65535 AV:96 vfd2kwh_1
VFD2 Cumulative Run Time VFD2RUNT R hr 0 to 65535 AV:97 vfd2runt_1
VFD2 DC Bus Voltage VFD2VDC R V 0 to 1000 AV:99 vfd2vdc_1
VFD2 Last Fault Code VFD2LFC R 0 to 65535 AV:100 vfd2lfc_1
VFD2 Output Voltage VFD2VOUT R V 0 to 1000 AV:102 vfd2vout_1
VFD2 Status Word 1 VFD2STAT R 0 to 0 AV:103 vfd2stat_1
VFD2 Transistor Temp (C) VFD2TEMP R 0 to 150 AV:104 vfd2temp_1
VFD-IGV Fire Speed Override STATPFSO W % 100 0 to 100 AV:187 statpfso_1
APPENDIX F — UPC OPEN CONTROLLER
Table AP — NETWORK POINTS LIST (cont)
POINT DESCRIPTION
CCN POINT
NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET OBJECT
NAME
BP Building Pressure OAEC Outdoor Air Enthalpy Changeover
DBC Dry Bulb Changeover OAQ Outdoor Air Quality
DCV Demand Controlled Ventilation OAT Outdoor Air Temperature
DDBC Differential Dry Bulb Changeover R—Read
DEC Differential Enthalpy Changeover RAT Return Air Temperature
EDT Evaporator Discharge Temperature RH Relative Humidity
EXV Electronic Expansion Valve SASP Supply Air Set Point
IAQ Indoor Air Quality SPT Space Temperature
IGV Inlet Guide Vanes VAV Variable Air Volume
LAT Leaving Air Temperature VFD Variable Frequency Drive
n/a Not Available W—Write