240
APPENDIX G — OPTIONAL MOTORMASTER
®
V CONTROL
Fig. R — Motormaster
®
V Wiring (48/50P070-100 Units Shown)
Drive Programming
Table AR shows all program parameters for each of the operat-
ing modes. Refer to Troubleshooting section before attempting
to change programming in the Motormaster V control.
TO ENTER PASSWORD AND CHANGE PROGRAM
VALUES:
1. Press MODE.
2. The display will read “00” and the upper right-hand deci-
mal point will be blinking. This will activate the PASS-
WORD prompt (if the password has not been disabled).
3. Use the UP and DOWN buttons to scroll to the password
value (the factory default password is “111”) and press the
MODE button. Once the correct password value is
entered, the display will read “P01”, which indicates that
the PROGRAM mode has been accessed at the beginning
of the parameter menu (P01 is the first parameter).
NOTE: If the display flashes “Er”, the password was incorrect,
and the process to enter the password must be repeated.
4. Press MODE to display present parameter setting. The
upper right decimal point will blink. Use UP and DOWN
buttons to scroll to the desired parameter number.
5. Once the desired parameter number is found, press the
MODE button to display the present parameter setting.
The upper right-hand decimal point will begin blinking,
indicating that the present parameter setting is being dis-
played. Use the UP and DOWN buttons to change setting.
Press MODE to store new setting.
6. Press MODE to store the new setting and also exit the
PROGRAM mode. To change another parameter, press the
MODE button again to re-enter the PROGRAM mode (the
parameter menu will be accessed at the parameter that was
last viewed or changed before exiting). If the MODE but-
ton is pressed within two minutes of exiting the PRO-
GRAM mode, the password is not required to access the
parameters.
7. After two minutes, the password must be entered in order
to access the parameters again.
TO CHANGE PASSWORD
Enter the current password, then change P44 to the desired
password.
LEGEND
CCB Control Circuit Breaker
LLT Liquid Line Transducer
MMF Motormaster V Fuses
MMR Motormaster Relay
MMV Motormaster V Control
OFM Outdoor-Fan Motor
MOTORMASTER START
CONTACT LOCATION
UNIT
VOLTAGE
TERMINAL
NUMBER
575-3-60 1
208-3-60 1
230-3-60 1
380-3-60 13A
460-3-60 1
OFM1 (030,035,050-060)
OFM3 (040,070,075)
OFM6 (090,100)
21
23
11
13
BLK
RED
BLU
1
2
3
YEL
BLK
BLU
22
12
BLK
BLU
YEL
T1
T2
T3
BLK
2
*
RED
CCB
MMR-A
14
11
BLK
RED
BLU
1
2
3
BLK
BLU
YEL
T1
T2
T3
2
*
A
C
B
+
-
RED
LLT-A
BLK
GRN
L1
625
MMV-A
MMF-A
L2
L3
BLK
BLU
YEL
A
C
B
+
-
RED
LLT-B
BLK
GRN
L1
625
MMV-B
MMF-B
L2
L3
BLK
BLU
YEL
OFM1 (070,075)
OFM2 (090,100)
070-100 ONLY
SEE TABLE FOR START CONTACT LOCATION
SEE TABLE FOR START CONTACT LOCATION
PL31-3
PL31-4
PL60-1
PL60-2
BLK
RED
MMR-B
14
11
PL31-5
PL31-6
PL60-3
PL60-4
CAUTION
UNIT DAMAGE HAZARD
It is strongly recommended that the user NOT change any
programming without consulting Carrier service personnel.
Unit damage may occur from improper programming.