Table 29 — Service Test
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
TEST Service Test Mode ON/OFF MAN_CTRL
STOP Local Machine Disable YES/NO UNITSTOP config
S.STP Soft Stop Request YES/NO SOFTSTOP forcible
FAN.F Supply Fan Request YES/NO SFANFORC forcible
INDP TEST INDEPENDENT OUTPUTS
HUM.R Humidifier Relay ON/OFF HUMR_TST
ALRM Remote Alarm/Aux Relay ON/OFF ALRM_TST
FANS TEST FANS
F.MOD Fan Test Automatic? YES/NO FANAUTO
E.POS Econo Damper Command Pos % ECONFANS
S.FAN Supply Fan Relay ON/OFF SFAN_TST
S.VFD Supply Fan Commanded % 0 to 100 % SFVFDTST
P.E.1 Power Exhaust Relay 1 ON/OFF PE1_TST
E.VFD Exhaust Fan Commanded % 0 to 100 % EFVFDTST
P.E.2 Power Exhaust Relay 2 ON/OFF PE2_TST
BP1.C BP 1 Command Position 0 to 100 % BLDPTST1
BP2.C BP 2 Command Position 0 to 100 % BLDPTST2
CDF.1 Condenser Fan Output 1 ON/OFF CND1_TST
CDF.2 Condenser Fan Output 2 ON/OFF CND2_TST
CDF.3 Condenser Fan Output 3 ON/OFF CND3_TST
CDF.4 Condenser Fan Output 4 ON/OFF CND4_TST
AC.T.C CALIBRATE TEST-ACTUATORS
ECN.C Economizer Act.Cmd.Pos. 0 to 100 % ECON1TST
EC.CL Economizer Calibrate Cmd YES/NO ECONOCAL
ECN.A Econ Act. Control Angle read only ECONCANG
EC2.C Economzr 2 Act.Cmd.Pos. 0 to 100 % ECON2TST
E2.CL Economzr 2 Calibrate Cmd YES/NO ECON2CAL
EC2.A Econ2 Act.Control Angle read only ECN2CANG
BP1.C BP 1 Command Position 0 to 100 % BLDG1TST
B1.CL BP 1 Actuator Cal Cmd YES/NO BLDG1CAL
BP1.A BP Act.1 Control Angle read only BP1_CANG
BP1.M BP 1 Actuator Max Pos. 0 to 100 % BP1SETMX
BP2.C BP 2 Command Position 0 to 100 % BLDG2TST
B2.CL BP 2 Actuator Cal Cmd YES/NO BLDG2CAL
BP2.A BP Act.2 Control Angle read only BP2_CANG
BP2.M
BP 2 Actuator Max Pos. 0 to 100 % BP2SETMX
HTC.C Ht.Coil Command Position 0 to 100 % HTCLACTC
HT.CL Heating Coil Act. Cal.Cmd YES/NO HCOILCAL
HTC.A Heat Coil Act.Ctl.Angle read only HTCLCANG
HMD.C Humidifier Command Pos. 0 to 100 % HUMD_TST
HM.CL Humidifier Act. Cal.Cmd YES/NO HUMIDCAL
HMD.A Humidifier Act.Ctrl.Ang. read only HUMDCANG
HMZR TEST HUMIDIMIZER
RHV Humidimizer 3-Way Valve ON/OFF RHVH_TST
C.EXV Condenser EXV Position 0 to 100 % CEXVHTST
B.EXV Bypass EXV Position 0 to 100 % BEXVHTST
C.CAL Condenser EXV Calibrate ON/OFF CEXV_CAL
B.CAL Bypass EXV Calibrate ON/OFF BEXV_CAL
COOL TEST COOLING
E.POS Econo Damper Command Pos 0 to 100 % ECONCOOL
SP.SP Static Pressure Setpoint 0 to 5 " H2O SPSP_TST
CL.ST Requested Cool Stage 0 to n CLST_TST
MLV Minimum Load Valve Relay ON/OFF MLV_TST
A1 Compressor A1 Relay ON/OFF CMPA1TST
A1.CP Compressor A1 Capacity 20 to 100 A1CAPTST
A1.B1 Two Circuit Start A1,B1 ON/OFF CMPABTST
A2 Compressor A2 Relay ON/OFF CMPA2TST
A3 Compressor A3 Relay ON/OFF CMPA3TST
B1 Compressor B1 Relay ON/OFF CMPB1TST
B2 Compressor B2 Relay ON/OFF CMPB2TST
B3 Compressor B3 Relay ON/OFF CMPB3TST
RHV Humidimizer 3-Way Valve ON/OFF RHVH_TST
C.EXV Condenser EXV Position 0 to 100 % CEXVHTST
B.EXV Bypass EXV Position 0 to 100 % BEXVHTST
HEAT TEST HEATING
HT.ST Requested Heat Stage 0 to n HTST_TST
HT.1 Heat Relay 1 ON/OFF HS1_TST
H1.CP Modulating Heat Capacity 0 to 100 % MGAS_TST
HT.2 Heat Relay 2 ON/OFF HS2_TST
HT.3 Relay 3 W1 Gas Valve 2 ON/OFF HS3_TST
HT.4
Relay 4 W2 Gas Valve 2 ON/OFF HS4_TST
HT.5 Relay 5 W1 Gas Valve 3 ON/OFF HS5_TST
HT.6 Relay 6 W2 Gas Valve 3 ON/OFF HS6_TST
H.I.R Heat Interlock Relay ON/OFF HIR_TST
HTC.C Ht.Coil Command Position 0 to 100 % HTCLHEAT