81
Table 66 — Building Pressure Configuration
*Some configurations are model number dependent.
Building Pressure SETP (BP.SP)
This set point is the building pressure control set point. If the
unit is configured for a type of modulating building pressure
control, then this is the set point that the control will control to.
BP Setpoint Offset (BP.SO)
For building pressure configurations BP.CF=2, 3, and 4, this is
the offset below the building pressure set point that the build-
ing pressure must fall below to turn off power exhaust control.
Power Exhaust on Setp.1 (BP.P1)
When configured for building pressure control type BP.CF = 1
(constant volume two-stage control), the control will turn on
the first power exhaust fan when the economizer’s position ex-
ceeds this set point.
Power Exhaust on Setp.2 (BP.P2)
When configured for building pressure control type BP.CF = 1
(constant volume two-stage control), the control will turn on
the second power exhaust fan when the economizer’s position
exceeds this set point.
VFD/Act. Fire Speed/Pos (BP.FS)
For BP.CF = 2, 3, 4, and 5, this configuration is the VFD
speed/actuator position override when the control is in the
purge and evacuation smoke control modes.
VFD/Act. Min Speed/Pos (BP.MN)
For BP.CF = 2, 3, 4, and 5, this configuration is the minimum
VFD speed/actuator position during building pressure control.
VFD Maximum Speed/Pos (BP.MX)
For BP.CF = 3 and 5, this configuration is the maximum VFD
speed during building pressure control.
BP 1 Actuator Max Pos. (BP.1M)
For BP.CF = 2, this configuration is the maximum actuator no.
1 position during building pressure control.
BP 2 Actuator Max Pos. (BP.2M)
For BP.CF = 2, this configuration is the maximum actuator no.
2 position during building pressure control.
BP Hi Cap VFD Clamp Val. (BP.CL)
For BP.CF = 4, this configuration is a limit that creates a deadband
which controls the action of the second power exhaust relay.
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT
BP BUILDING PRESS. CONFIGS
BP.CF Building Press. Config 0 to 5 BLDG_CFG 0*
BP.S Building Pressure Sensor Enable/Disable BPSENS Disable*
BP.R Bldg. Press. (+/-) Range 0.10 to 0.25 " H2O BP_RANGE 0.25
BP.SP Building Pressure Setp. –0.25 to 0.25 " H2O BPSP 0.05
BP.SO BP Setpoint Offset 0 to 0.5 " H2O BPSO 0.05
BP.P1 Power Exhaust On Setp.1 0 to 100 % PES1 25
BP.P2 Power Exhaust On Setp.2 0 to 100 % PES2 75
B.V.A VFD/ACTUATOR CONFIG
BP.FS VFD/Act. Fire Speed/Pos. 0 to 100 % BLDGPFSO 100
BP.MN VFD/Act. Min.Speed/Pos. 0 to 50 % BLDGPMIN 10
BP.MX VFD Maximum Speed 50 to 100 % BLDGPMAX 100
BP.1M BP 1 Actuator Max Pos. 85 to 100 % BP1SETMX 100
BP.2M BP 2 Actuator Max Pos. 85 to 100 % BP2SETMX 100
BP.CL BP Hi Cap VFD Clamp Val. 5 to 25 % BLDGCLMP 10
FAN.T FAN TRACKING CONFIG
FT.CF Fan Track Learn Enable Yes/No DCFM_CFG No
FT.TM Fan Track Learn Rate 5 to 60 min DCFMRATE 15
FT.ST Fan Track Initial DCFM –20000 to 20000 CFM DCFMSTRT 2000
FT.MX Fan Track Max Clamp 0 to 20000 CFM DCFM_MAX 4000
FT.AD Fan Track Max Correction 0 to 20000 CFM DCFM_ADJ 1000
FT.OF Fan Track Internl EEPROM –20000 to 20000 CFM DCFM_OFF 0
FT.RM Fan Track Internal RAM –20000 to 20000 CFM DCFM_RAM 0
FT.RS Fan Track Reset Internal Yes/No DCFMRSET No
SCF.C Supply Air CFM Config 1 to 2 SCFM_CFG 1
B.PID BLDG.PRESS.PID CONFIGS
BP.TM Bldg.Pres.PID Run Rate 5 to 120 sec BPIDRATE 10
BP.P Bldg.Press. Prop. Gain 0 to 5 BLDGP_PG 0.5
BP.I Bldg.Press. Integ. Gain 0 to 2 BLDGP_IG 0.5
BP.D Bldg.Press. Deriv. Gain 0 to 5 BLDGP_DG 0.3
ACT.C BLDG.PRES. ACTUATOR CFGS
BP.1 BLDG.PRES. ACT.1 CONFIGS
SN.1 BP 1 Serial Number 1 0 to 9999 BP_1_SN1 0
SN.2 BP 1 Serial Number 2 0 to 6 BP_1_SN2 0
SN.3 BP 1 Serial Number 3 0 to 9999 BP_1_SN3 0
SN.4 BP 1 Serial Number 4 0 to 254 BP_1_SN4 0
C.A.LM BP1 Cntrl Angle Lo Limit 0 to 90 BP1_CALM 35
BP.2 BLDG.PRES. ACT.2 CONFIGS
SN.1 BP 2 Serial Number 1 0 to 9999 BP_2_SN1 0
SN.2 BP 2 Serial Number 2 0 to 6 BP_2_SN2 0
SN.3 BP 2 Serial Number 3 0 to 9999 BP_2_SN3 0
SN.4 BP 2 Serial Number 4 0 to 254 BP_2_SN4 0
C.A.LM BP2 Cntrl Angle Lo Limit 0 to 90 BP2_CALM 35