Table 67 — Indoor Air Quality Configuration
IAQ Discrete Fan Config (Configuration
IAQ
AQ.CF

IQ.I.F)
This is used to configure the operation of the fan during an
IAQ demand condition. It has the following configurations:
IQ.I.F = 0 (No Fan Start) — IAQ demand will never over-
ride normal indoor fan operation during occupied or unoc-
cupied period and turn it on.
IQ.I.F = 1 (Fan On If Occupied) — IAQ demand will
override normal indoor fan operation and turn it on (if off)
only during the occupied period (CV operation with auto-
matic fan).
IQ.I.F = 2 (Fan On Occupied/Unoccupied) — IAQ de-
mand will always override normal indoor fan operation
and turn it on (if off) during both the occupied and unoccu-
pied period.
Economizer Min Position (Configuration
IAQ
DCV.C

EC.MN)
This is the fully occupied minimum economizer position.
IAQ Demand Vent Min Pos. (Configuration
IAQ

DCV.C
IAQ.M)
This configuration will be used to set the minimum damper po-
sition in the occupied period when there is no IAQ demand.
IAQ Econo Override Pos (Configuration
IAQ
AQ.SP
IQ.O.P)
This configuration is the position that the economizer goes to
when override is in effect.
OAQ Lockout Value (Configuration
IAQ
AQ.SP
OAQ.L)
This is the maximum OAQ level above which demand ventila-
tion will be disabled.
Diff. Air Quality Lo Limit (Configuration
IAQ

AQ.SP

DAQ.L)
This is the differential CO
2
level at which IAQ control of the
dampers will be initiated.
Diff. Air Quality Hi Limit (Configuration
IAQ

AQ.SP

DAQ.H)
This is the differential CO
2
level at which IAQ control of the
dampers will be at maximum and the dampers will be at the
Configuration
IAQ
DCV.C
EC.MN.
DAQ ppm Fan On Set Point (Configuration

IAQ

AQ.SP
D.F.ON)
This is the CO
2
level at which the indoor fan will be turned on.
DAQ ppm Fan Off Set Point (Configuration
IAQ
AQ.SP
D.F.OF)
This is the CO
2
level at which the indoor fan will be turned off.
IAQ Low Reference (Configuration
IAQ
AQ.S.R
IQ.R.L)
This is the reference that will be used with a to non-Carrier
IAQ sensor that may have a different characteristic curve. It
represents the CO
2
level at 4 mA.
IAQ High Reference (Configuration
IAQ
AQ.SR

IQ.R.H)
This is the reference that will be used with a non-Carrier IAQ
sensor that may have a different characteristic curve. It rep-
resents the CO
2
level at 4 mA.
OAQ Low Reference (Configuration
IAQ
AQ.S.R
OQ.R.L)
This is the reference that will be used with a non-Carrier OAQ
sensor that may have a different characteristic curve. It rep-
resents the CO
2
level at 4 mA.
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT
DCV.C DCV ECONOMIZER SETPOINTS
EC.MN Economizer Min.Position 0 to 100 % ECONOMIN 5
IAQ.M IAQ Demand Vent Min.Pos. 0 to 100 % IAQMINP 0
O.C.MX Economizer Min.Flow 0 to 20000 CFM OACFMMAX 2000
O.C.MN IAQ Demand Vent Min.Flow 0 to 20000 CFM OACFMMIN 0
O.C.DB Econ.Min.Flow Deadband 200 to 1000 CFM OACFM_DB 400
AQ.CF AIR QUALITY CONFIGS
IQ.A.C IAQ Analog Sensor Config 0 to 4 IAQANCFG 0
IQ.A.F IAQ 4-20 ma Fan Config 0 to 2 IAQANFAN 0
IQ.I.C IAQ Discrete Input Config 0 to 2 IAQINCFG 0
IQ.I.F IAQ Disc.In. Fan Config 0 to 2 IAQINFAN 0
OQ.A.C OAQ 4-20ma Sensor Config 0 to 2 OAQANCFG 0
AQ.SP AIR QUALITY SETPOINTS
IQ.O.P IAQ Econo Override Pos. 0 to 100 % IAQOVPOS 100
IQ.O.C IAQ Override Flow 0 to 31000 CFM IAQOVCFM 10000
DAQ.L Diff.Air Quality LoLimit 0 to 1000 DAQ_LOW 100
DAQ.H Diff. Air Quality HiLimit 100 to 2000 DAQ_HIGH 700
D.F.OF DAQ PPM Fan Off Setpoint 0 to 2000 DAQFNOFF 200
D.F.ON DAQ PPM Fan On Setpoint 0 to 2000 DAQFNON 400
IAQ.R Diff. AQ Responsiveness –5 to 5 IAQREACT 0
OAQ.L OAQ Lockout Value 0 to 2000 OAQLOCK 0
OAQ.U User Determined OAQ 0 to 5000 OAQ_USER 400
AQ.S.R AIR QUALITY SENSOR RANGE
IQ.R.L IAQ Low Reference 0 to 5000 IAQREFL 0
IQ.R.H IAQ High Reference 0 to 5000 IAQREFH 2000
OQ.R.L OAQ Low Reference 0 to 5000 OAQREFL 0
OQ.R.H OAQ High Reference 0 to 5000 OAQREFH 2000
IAQ.P IAQ PRE-OCCUPIED PURGE
IQ.PG IAQ Purge Yes/No IAQPURGE No
IQ.P.T IAQ Purge Duration 5 to 60 min IAQPTIME 15
IQ.P.L IAQ Purge LoTemp Min Pos 0 to 100 % IAQPLTMP 10
IQ.P.H IAQ Purge HiTemp Min Pos 0 to 100 % IAQPHTMP 35
IQ.L.O IAQ Purge OAT Lockout 35 to 70 dF IAQPNTLO 50