Programming specific applications
ZS Sensor CARRIER CORPORATION ©2020
Applications Guide All rights reserved
22
ZS Pro-F: To program manual fan speed control using the button
NOTE
The ZS Pro-F's button works only when the zone is occupied (green LED is on).
To program the sensor's
button:
1 From the
Sys In
microblock menu, add a
BACnet Multi-State Value Parameter
microblock.
2 On the Property Editor's
Rnet
tab, check
Enable Rnet
.
3 Select the
Fan Speed Request (600)
from the
Rnet Tag
drop-down list.
4 Check
Editable
.
5 On the
Properties
tab in the
Rnet Text
fields, type the text that you want to a sensor to show for each fan
speed.
NOTES
The letters K, M, Q, W, X do not display on a screen.
If you do not enter text, the sensor will show the Value number for the fan speed.
When a user presses the
button, the screen initially shows the current fan speed. With each press of the
button, the display shows one of the following options:
Auto. The control program determines the speed.
Low speed
Medium speed
High speed
ZS Pro: To program manual fan speed control using the or button
1 From the
Sys In
microblock menu, add a
BACnet Multi-State Value Parameter
microblock.
2 On the Property Editor's
Rnet
tab, check
Enable Rnet
.
3 Select the
Fan Speed Request (600)
from the
Rnet Tag
drop-down list.
4 Check
Editable
.

Other manuals for Carrier ZS Pro