EasyManuals Logo

CBI CH Series User Manual

CBI CH Series
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
17
Start-up
CHECKS WITH THE FAN RUNNING
Speed of the impeller
The impeller rotation speed limit is specied in the job documents as well in At-
tachment Ex and on the fan plate.
Fan ow rate and partialisation of the ow.
The ow adjustment systems must be opened and closed
slowly so as to avoid the risk of generating sparks which
can create the risk of explosion.
Indicatively, do not perform individual opening or closing
adjustments in less than 1 second.
First start-up
After the rst start-up you must:
- Measure the vibrations.
- Measure the temperature of the bearings.
- Measure the speed of rotation of the impeller or of the transmission shaft.
N.B. Refer to the INSPECTIONS chapter in this manual and the user and standard
basic maintenance manual related to your fan model.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CBI CH Series and is the answer not in the manual?

CBI CH Series Specifications

General IconGeneral
BrandCBI
ModelCH Series
CategoryFan
LanguageEnglish

Related product manuals