Page: 13 of 15
*** Only required when radiant cooling is used.
Parameter Description
Value
Default Set To
4410
Compensation of room humidity***
0 = Disable
1 = Enable
1 1
4411
Room relative humidity value to start increasing
Outgoing water temperature set point***
55 40
4412
Maximum outgoing temperature hysteresis corresponding
to 100% relative humidity***
40 15
5107
Enable DHW sensor: Terminal 7-8
0 = Disable
1 = Enable
0 1
5117
Terminal 17-18: Humidity sensor
0 = Disable
1 = Enable
0 1
5120
Terminal 20-21: On/O remote contact or EHS Alarm input
0 = Disable (Remote controller only)
1 = On/O remote contact
2 = EHS Alarm input
0 1
5124
Terminal 24-25: Heating/Cooling mode remote contact
0 = Disable (Remote Controller Only)
1 = Cooling is CLOSE contact, Heating is OPEN contact
2 = Cooling is OPEN contact, Heating is CLOSE contact
0 1
5126
Flow switch input, terminals 26-27:
0 = Disable
1 = Enable
1 0
5150
Enable DHW 3-way valve: Terminal 50-51-52
0 = Disable
1 = Enable
0 1
System D: Heat Pump Switched On/O by Room
Thermostat(s) Heating & Cooling + DHW continued