Loading...
F0.01
Command
Source
0Integral Keypad
1Digital Terminal
2Communication
3Remote Panel
0
F0.02
Main
Frequency
Reference
0Digital Given
1AI1
2AI2
3Reserve
4High Speed Pulse HDI Reference
5Preset Speed Reference
6Simple PLC Reference
7Close Loop PID Reference
8Reserve
9Potentiometer Reference
0
F0.05
Digital Given
F0.09-Min. FrequencyF0.08-Max. Frequency
5.00Hz
F0.14
Accelerate
Time 1
0.06500.0s
Depend on
Series
F0.15
Decelerate
Time 1
0.06500.0s
Depend on
Series
F0.20
Parameter
Factory Default
0No Effect
1Fault Log Clear
2 Set to Factory Default Except Motor NP
Parameters and Parameter F7.11
3Reset Custom Parameter Group to Factory
Default Except Motor NP Parameters and
Parameter F7.11
4All Parameter Reset to Factory Default
5Back Up Parameters
6Using Back Up Parameters
7Saving Back Up Parameters
Note Only when you are using backup
parameters,backup parameter are able to be
saved.Otherwise when power off then re-power
the inverter,except the updated parameters other
parameters are always initial value.
0
F2.00
Motor Type
0AC Induction Motor
1Reserve
2Reserve
F2.01
Motor NP
Power
0.1 1000.0 kW
Depend on
motor type
F2.02
Motor NP
Voltage
0V Inverter Rated Voltage
Depend on
motor type
F2.03
Motor NP
Current
0.11000.0A
Depend on
motor type
F2.04
Motor NP
Frequency
0.01Hz ~ F0.07
Depend on
motor type
F2.05
Motor Poles
2 24
4
F2.06
Motor NP RPM
060000rpm
1430rpm
F2.22
Motor Auto
Tuning
0No Operation
1Static Tune
2Rotate Tune
0
F7.11
Parameter
Menu Mode
1Simple Menu Mode
2Custom Menu Mode
3Engineering Menu Mode
1