Chromalox 2104 Technical Manual 49
ENTIENTI
ENTIENTI
ENTI
RSP RSP
RSP RSP
RSP
AUX ▲▼
RESET
☛
Alarm
Relay
Action
Output Relays #3, #4 and #5 can be set to be normally
energized or de-energized, latching or non-latching. A
normally de-energized relay is in its non-energized
state when not in alarm. For example, Outputs #3 and
#4 are normally-open contacts. When setup as
normally de-energized, the relays will be open when
not in alarm, and closed when in alarm.
A non-latching relay will not stay in alarm if the alarm
condition goes away. A latching relay will not go out
of alarm until the alarm condition no longer exists and
is pressed.
RESET
Alarm
Operation
Latching alarms can be reset by pressing the RESET
pushbutton on the controller front panel. The alarm
cannot be reset until the process is out of the alarm
condition. The Digital Input can be setup to function
as a remote alarm reset button (see pages 59-63).