64 Chromalox 2104 Technical Manual
AUX Key
(continued)
PID2PID2
PID2PID2
PID2 = PID2 Enabled
This function can be used in single output control
applications only (CTRL PAGE CONT = HEAT or
COOL). When this function is selected, pressing the
AUX Key will toggle between PID1 (CTRL PAGE,
menus PB1, AR1, RAT1) and PID2 (CTRL PAGE, menus
PB2, AR2, RAT2) parameters. If the power is
interrupted, the last active PID parameters will be
used when power is restored. The AUX indicator is
ON when PID2 parameters are selected and OFF
when PID1 parameters are selected.
AA
AA
A
USPUSP
USPUSP
USP = Auxiliary Setpoint Enable
When this function is selected, pressing the AUX
Key will toggle between the Auxiliary and Local
setpoints. If the power is interrupted, the last active
setpoint will be used when power is restored. The
AUX indicator is ON when the Auxiliary Setpoint
is selected and OFF when the Local Setpoint is
selected. The setpoints are adjustable in Operator
Mode according to security. This function cannot be
used when Ramp/Soak is enabled.
RSPRSP
RSPRSP
RSP = Remote Setpoint Enable
When this function is selected, pressing the AUX
Key will toggle between the Remote and Local
Setpoints. If the power is interrupted, the last active
setpoint will be used when power is restored.
Remote setpoint must be enabled (CTRL PAGE,
RSP = ON) for this function to operate. The AUX
indicator is ON when the Remote Setpoint is
selected and OFF when the Local Setpoint is
selected. This function cannot be used when
Ramp/Soak is enabled.