15
English

Before installation, check strength and horizontality of the
base so that abnormal sound does not generate.
According to the dimensions and clearances, x the base
rmly with the anchor bolts (Anchor bolt, nut: M10 x 2
pairs).
If the outdoor unit is installed in a very windy place,
protect the fan with a wind protection screen and check
that it works correctly.
5.1 - Opening cable knockouts (Fig. 4)
There is a pre-cut part that can be removed for running
wires.
Do not remove the unit front panel for easier drilling of
the knockouts. The pre-cut section of the sheet can be
removed by punching the 3 connection points along the
line rst using a chisel and nally with pliers (see g. 4).
When the cable knockout is open, remove the burrs and t
the cable protective bush supplied with the unit for cable
protection.
5.2 - How to remove the front panel (Fig. 5)
1. Remove screws of the front panel (See g 5).
2. Pull the front panel downward with the handle.
5.3 - Drain hose and base pan knockouts (Fig. 6)
See g. 6.
In case of draining through the drain hose, attach the drain
nipple (A) and use the drain hose (Inner diam.: 16mm)
sold in the market. When there is a possibility of freezing
of drain at the cold district or a snowfall area, be careful
for drainage ability of drain.
The drainage ability increases when knockout holes on the
base pan are opened. (Open the knockout hole to outside
using a soft-faced hammer (B), etc.).
5.4 - Operating limits (Fig. 7/8)
Operation in cooling: See g. 7



Operation in heating: See g. 8

Unit
EREBA
4H 6H 8H 12H/HT 15H/HT
Compressor Type Rotary DC Inverter Tecnology
Water pump speed Three speed
Expansion vessel
Capacity l 2 3
Nitrogen precharge pressure kPa 200
Net water volume l 1 1 1.2 2.5 2.5
Water connections 1''M
Maximum water pressure kPa 300

Table of Contents