10.1
Operating
ranges
A - Full load operation
with pure water
B - Full load operation
must be with glycol
C - Operation without
HPS
D - Partial load
operation (AUTO-
ADAPTIVE)
10.2 Condenser limits
IMPORTANT: To ensure that LW - LWP units operate correctly,
especially during the start-up phases, with a condenser cold
water loop, a device must be fitted to ensure a minimum
condenser fluid inlet temperature of 20°C is reached very
quickly (e.g. 3-way valve).
10.3 Evaporator limits
The curve shows the minimum and maximum allowable
temperature differences for pure water or glycol water according
to the evaporator fluid outlet temperature. Also check the
minimum and maximum temperature differences according
to the requisite minimum and maximum flow rates (see table,
section 10.4 Minimum/maximum water flow rates).
1
-8 -6 -4 -2 0246810
12
6
5
2
3
4
7
8
9
Tubular evaporator
Water outlet temperature (°C)
Δ T maximum
Δ T minimum
ΔT acceptable evaporator water
inlet/outlet difference (°C)
difference taken into account in the performance tables.
Example:
For water outlet: + 5°C (design Δt 5°C)
Minimum ΔT: 3.1°C Water temp.: 8.1 / 5°C
Maximum ΔT: 7.2°C Water temp.: 12.2 / 5°C
- An excessively low flow rate can be a fouling factor; an excessively high flow rate can cause erosion phenomena.
11 - LOCATION OF THE MAIN COMPONENTS
LW - LWP 1800BX to 2800BX LW - LWP 3050BX to 4800BX
HYDROCIAT LW LWP
ΔT minimum°C 5
ΔT maximum°C 10
Evaporator
Electrical cabinet Manifold (Optional)
Manifold (Optional)
Desuperheater (Optional)
Condensers
Compressor N° 2Compressor N° 1
Compressor N° 2
Compressor N° 1
Electrical cabinet
Manifold (Optional)Manifold (Optional)
Desuperheater (Optional)
Evaporator
Circ. 1
condenser
Circ. 2
condenser
Electrical cabinet Manifold (Optional)
Manifold (Optional)
Condensers
Desuperheater (Optional)
Desuperheater (Optional)
Evaporator
Compressor
N° 2
Compressor
N° 1
Compressor N° 2
Compressor N° 1
Electrical cabinet
Manifold (Optional)
Manifold
(Optional)
Desuperheater (Optional)
Evaporator
Circ. 1 condenser
Circ. 2 condenser
30
35
40
45
50
55
60
65
-8 -4 0510 15-10
AB
C
D
25
Condenser water outlet temperature°C
Glycol required
Evaporator water outlet temperature°C
10.4 Minimum/maximum water flow rates
The flow rates in the exchangers must be maintained between the values given below.
HYDROCIAT
LW - LWP
1800BX
(HPS)
2150BX
(HPS)
2500BX
(HPS)
2800BX
(HPS)
3050BX
HPS
3500BX
HPS
3600BX
HPS
3900BX
HPS
4200BX
HPS
4500BX
HPS
4800BX
HPS
Condenser
min. m
3
/h 40 40 40 43 54
max. m
3
/h 140 166 192 232 288
Evaporator
min. m
3
/h 50 80 80 80 80 80
min. m
3
/h 150 231 246 231 246 293
10 - OPERATING LIMIT