WIRING
PCI main terminal
RESET ENABLE/DISABLE:
Disable - will not allow any fault to be reset.
Enable - any fault can be reset from the keypad or the remote
reset button.
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9 10
Disable Enable
Reset
Remote
Reset
not required
Connect input to
ground if not
needed. (Reset
always enabled).
15VDC
PCI MAIN TERMINAL
Connections 1 and 3 of the PCI main
terminal are to be connected in the
field as needed. All other main
terminal connections are factory
wired when ordered in a NEMA
enclosure.
14 14
POWER SUPPLY
LOW VOLTAGE I/O TERMINAL
FACTORY CONNECTED
PCI TERMINAL DESCRIPTION
1 reset supervisory input
2 clutch/brake status input
3 remote reset input
4 not connected
5 fault/batch output
6 limit switch 2 output
7 limit switch 3 output
8 limit switch 4 output
9 limit switch 1 output
10 +15VDC input