© 2013 Cisco and/or its affiliates. All rights reserved. This document is Cisco Public Information. Page 7 of 11
Power Supply 1300W AC 2800W AC 4200W AC 6000 AC 9000 AC 1400W DC with Power Entry
Module (PEM)
Output current
(PoE)
-50V at 16.7A -50V at 28A -50V at 77.1A
(200V)
-50V at 38A
(100V)
-50V at 100.0A
(200V)
-50V at 38.5A
(120V)
-50V at 150.0A
(200V)
-50V at 50.0A
(120V)
140A at -48/-60 VDC
Output power
redundant mode
(data)
1000W + 40W 1360W + 40W 1383W + 40W 2200W + 40W 1960W + 40W 1360W + 40W
Output power
redundant mode
(PoE)
800W
maximum per
power supply
1400W
maximum per
power supply
●
3700W
(220V)
●
1850W
(110V)
●
4800W
(220V)
●
1850W
(110V)
●
7500W
(220V)
●
2500W
(110V)
Up to 7500W (minus the power
consumed for data)
Output power
combined mode
(data)
1667W 2473W 2766W 4400W 3920W -
Output power
combined mode
(PoE)
1333W 2333W 6700W (220V)
3360W (110V)
8700W (220V)
3360W (110V)
14,400W
(220V)
4150W (110V)
3800W (100V)
Heat dissipation 1568 BTU/hr 2387 BTU/hr 3580 BTU/hr 2720 BTU/hr 3010
BTU/hr
Data only: 1591 Btus per hour
Data and voice: 2905 Btus per
hour
Holdup time 20 ms 20 ms 20 ms 20 ms 20 ms 4 ms
Hot swappable Yes Yes Yes Yes Yes Yes
Additional notes for Tables 7 and 8:
●
Output power is per power supply unless otherwise stated.
●
Heat-dissipation numbers represent the power-conversion losses of the power supply in operation.
●
The number of power devices supported depends on customer configuration.
Fan Trays
Each Cisco Catalyst 4500E Series uses a single fan tray for cooling. All fan trays are composed of independent
fans. If one fan fails, the system will continue to operate without a significant degradation in cooling. The system
will detect and notify the user (through LED, CLI, and Simple Network Management Protocol [SNMP]) that a fan
has failed and the tray needs to be replaced.
Environmental Conditions
The Cisco Catalyst 4500 and 4500E Series require the following conditions:
●
Operating temperature: 32 to 104ºF (0 to 40ºC)
●
Storage temperature: -40 to 167ºF (-40 to 75ºC)
●
Relative humidity: 10 to 90 percent, noncondensing
●
Operating altitude: -60 to 3000 meters (m)