Site Requirements
Planning a proper location for the switch and layout of the equipment rack or wiring closet is essential for
successful system operation. These sections describe some of the basic site requirements that you should be
aware of as you prepare to install your switch, including the following:
Environmental factors can adversely affect the performance and longevity of your system.
Install the switch in an enclosed, secure area, ensuring that only qualified personnel have access to the
switch and control of the environment.
Equipment that is placed too closely together or that is inadequately ventilated may cause system
over-temperature conditions, leading to premature component failure.
Poor equipment placement can make chassis panels inaccessible and difficult to maintain.
The switch requires a dry, clean, well-ventilated, and air-conditioned environment.
To ensure normal operation, maintain ambient airflow. If the airflow is blocked or restricted, or if the
intake air is too warm, an over-temperature condition may occur. The switch environmental monitor may
then shut down the system to protect the system components.
Multiple switches can be rack mounted with little or no clearance above and below the chassis. However,
when mounting a switch in a rack with other equipment, or when placing it on the floor near other
equipment, ensure that the exhaust from other equipment does not blow into the air intake vent of the
switch chassis.
Temperature
Temperature extremes may cause a system to operate at reduced efficiency and cause a variety of problems,
including premature aging and failure of chips, and failure of mechanical devices. Extreme temperature
fluctuations may also cause chips to become loose in their sockets. Observe the following guidelines:
Ensure that the chassis has adequate ventilation.
Do not place the chassis within a closed-in wall unit or on top of cloth, which can act as thermal insulation.
Do not place the chassis where it will receive direct sunlight, particularly in the afternoon.
Do not place the chassis next to a heat source of any kind, including heating vents.
Adequate ventilation is particularly important at high altitudes. Make sure that all the slots and openings
on the system remain unobstructed, especially the fan vent on the chassis.
Clean the installation site at regular intervals to avoid buildup of dust and debris, which may cause a
system to overheat.
If system is exposed to abnormally low temperatures, allow a two hour warm up period, in ambient
temperature no lower than 32°F (0 °C) before turning on.
Failure to observe these guidelines may damage the chassis' internal components.
Cisco Catalyst 9500 Series Switches Hardware Installation Guide
25
Preparing for Installation
Site Requirements

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Cisco Catalyst C9500-40X and is the answer not in the manual?

Cisco Catalyst C9500-40X Specifications

General IconGeneral
ModelC9500-40X
CategorySwitch
Product SeriesCatalyst 9500
Rack Units1 RU
StackingStackWise Virtual
SoftwareCisco IOS XE
DRAM16 GB
Flash Memory16 GB
Input Voltage100 to 240 VAC
Power Consumption400W
Ports40 x 10GE
Uplink Ports4 x 40G/100G QSFP28
Forwarding Rate1, 440 Mpps
Dimensions1.73 x 17.5 x 21.52 in. (4.4 x 44.5 x 54.7 cm)