Touch Pad Control
Setup & Commissioning
TEK600 Series Control Page 20
Setup Parameters
There are a series of available parameters that can be modified to tailor the control to meet the customer’s requirements.
Carefully read these tables before entering the maintenance modes.
There are a number of potential product classes that the touch
pad control system will control. The class is the first
requirement for selection when entering the maintenance
mode.
Parameter Tables
Water Management
Installer Maintenance Parameter Default OFF Value ON Value
Dump Delay after shutdown 1 01 00 = OFF 01= 1 hr
Pre-Cool 2 01 00 = OFF 01 = 1.5 min
Dump Interval 3 00 00 = OFF 01,02,03,04,05,06 =
1, 2, 4, 8, 12,24 hrs
Sump fill before Pre-fill 4 01 00= OFF 01 = 1.5 min
Appliance Class Code
Touch Pad Wall Control tP
Heater H
Evaporative A/C E
Refrigerative A/C C
Combined Heater - Cooler HC
Diagnostic Mode
Installer
Maintenance
Parameter
Fill Valve 1
Fill Valve & Pump 2
Fan Speed
Installer
Maintenance
Parameter Default Value
Range
Low Fan Speed 1 92 40 – FF
High Fan Speed 2 FF FF – 9b