EasyManua.ls Logo

CLIVET MC2-Y 105T - Capacity Correction Factor for Height Difference

CLIVET MC2-Y 105T
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
Page 58
8. Capacity Correction Factor for Height Difference
8.1 Heat pump models
Model
ID2-XY 35M
Pipe Length (m)
MC2-Y 35M
Cooling 5 10 20 25
Height difference
H (m)
Indoor Upper
than Outdoor
10 0.973 0.948 0.936
5 0.995 0.983 0.958 0.945
0 1.000 0.988 0.963 0.950
Outdoor Upper
than Indoor
-5 1.000 0.988 0.963 0.950
-10 0.988 0.963 0.950
Heating 5 10 20 25
Height
difference
H (m)
Indoor Upper
than Outdoor
10 0.993 0.978 0.970
5 1.000 0.993 0.978 0.970
0 1.000 0.993 0.978 0.970
Outdoor Upper
than Indoor
-5 0.992 0.985 0.970 0.962
-10 0.977 0.962 0.955

Other manuals for CLIVET MC2-Y 105T

Related product manuals