EasyManuals Logo
Home>CLIVET>Air Conditioner>MC2-Y 160T

CLIVET MC2-Y 160T User Manual

CLIVET MC2-Y 160T
Go to English
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #84 background imageLoading...
Page #84 background image
36
Notions on refrigerant piping connection
6.1.4 Connect the pipes
When connecting the refrigerant pipes, be careful not to
use excessive torque or perform other operations that
may damage them. First connect the low pressure pipe
and then the high pressure pipe.
l
WARNING
When bending the connection pipes of the
refrigerant piping, observe a minimum radius
of 10 cm. See “Fig. 31”.
Radius > 10 cm
Fig. 31
TORQUES
Outer diameter of the pipe
(mm)
Tightening torque
(N•m)
Ø 6.35 (Ø 1/4") 14.2 - 17.2
Ø 9.52 (Ø 3/8") 32.7 - 39.9
Ø 12.7 (Ø 1/2") 49.5 - 60.3
Ø 15.9 (Ø 5/8") 61.8 - 75.4
m
CAUTION
DON'T USE EXCESSIVE TORQUE.
Excessive force can cause the nut to break or
damage the refrigerant piping. Do not exceed
the torque values shown in the table.
6.2 Connecting the pipes to the indoor
unit
1 Align the centre of the two pipes to be connected.
A
Indoor unit
piping
Flared nut Pipe
Fig. 32
2 Apply a little lubricating oil only to the inner surface of
the countersink (A).
3 Screw the flared nut by hand as far as possible.
4 Then fit the spanner round the nut.
5 Holding the nut firmly on the unit piping, use a torque
wrench to tighten the countersunk nut according to
the torque values in table “TORQUES”. Slightly loosen
the flared nut, then tighten it again.
Fig. 33

Table of Contents

Other manuals for CLIVET MC2-Y 160T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET MC2-Y 160T and is the answer not in the manual?

CLIVET MC2-Y 160T Specifications

General IconGeneral
BrandCLIVET
ModelMC2-Y 160T
CategoryAir Conditioner
LanguageEnglish

Related product manuals