26 MSAT-XEE 8.2-30.2 M09G60E14-04
8.6 Compressor supply line shut-o valve
Only if present
A. Supply line shut-o valve
CAUTION!
Do not remove the seal
Remove only if authorized by the manufacturer.
Please contact the maker for informations.
8.7 Control check list
intervention frequency (months) 1 6 12
1 presence corrosion X
2 panel xing X
3 fan xing X
4 coil cleaning X
5 check of the xing and the insulation of the power lead X
6 check of the earthing cable X
7 electric panel cleaning X
8 capacity contactor status X
9 termina closing, cable insulation integrity X
10 voltage and phase unbalancing (no load and on-load) X
11 absorptions of the single electrical loads X
12 test of the compressor crankcase heaters X
13 leak control* X
14 survey of the refrigerant circuit operating parameters X
15 protective device test: pressure switches, thermostats, ow switches etc.. X
16 control system test: setpoint, climatic compensations, capacity stepping, water / air ow-rate variations X
17 control device test: alarm signalling, thermometers, probes, pressure gauges etc.. X
* European regulation 303/2008
Refer to the local regulations; and ensure correct adherance. Companies and technicians that eect interventions of installation, maintenance/
repairs, leak control and recovery must be CERTIFIED as expected by the local regulations. The leak control must be eected with annual
renewal.
8.8 Air coil
Contact with the exchanger ns can cause cuts: wear protective gloves to perform the above described operations.
It is extremely important that the battery gives the maximum thermal exchange; therefore, its surface must be cleaned from dust and deposits.
Remove all impurities from the surface.
Using an air pressure gun, clean the aluminum surface of the battery; be careful to direct the air in the opposite direction of the fan air
movement.
Hold the gun parallel to the ns to avoid damages.
As an alternative, vacumn cleaner can be used to suck impurities from the air input side.
Verify that the aluminum ns are not bent or damaged, in the event of damages contact the authorized assistance center and get the ns
straightened in order to restore the initial condition for an optimal air ow.