6 - START-UP
6.15 HEATER IN REPLACEMENT
Configuration parameters
13 CaldaiaEn
Enable boiler function + heat pump
558 SogliaMaxImp
Water temp: over it the heat pump
is disabled.
Closed valves on Heat pump side
559 IsteresiSMI
Hysteresis for Heat pump enabling.
Opened valves on Heat pump side
560 SogliaExtC
Outside temperature threshold:
under it the boiler is enabled
561 IsteresiExt
External temperature hysteresis for
heat pump re-activation
562 TimeBypassALM
Transition time for alarm from heat
pump
6.16 HEATER IN INTEGRATION
Configuration parameters
18 EnPaux Aux. heater enabling
646 PotRes Power provided by the integration
resistances
647 LimText Ext. temperature limit for compressor
operation
648 Tregime Resistance Timeout
649 MaxInteg Max. analogical output value of the
integration res. when activated at the
same time of the compressor
650 MinInteg Min. analogical output value of the
integration res. in modulation
651 OffsetOnAux Step difference offset for aux
connection
652 TextOnAux Ext. temperature limit for auxiliary
operation
6.17 DOMESTIC HOT WATER
Configuration parameters
12 EnH2OSanitaria
Enabling of the DHW
management
410 SanitariaHeatMode
Management for DHW forced
production at satisfied system
thermoregulation in heat
411 DelayValvS
Opening time of the DHW valve
412 CompExtH2OS
Enabling of compensation for
outside temperature of the DHW
setpoint
413 MaxCompH2OS
Max. outside T correction value
for DHW setpoint
414 PriorCoolH2OSan
0=DHW priority ,1=system priority
415 PriorHeatH2Osan
0=DHW priority ,1=system priority
416 ComandoVSan
DHW valve management:
0=Managed according to the logic
fixed by EnH2oSanitaria, 1= In
Heat always excited, 2= In Cool
always excited
417 SetH2OSanitaria
DHW Set Point
428 TimeAntiLoop
Max permanence time in DHW
during the Antiloop control
430 DeltaChiller
Delta for DHW setpoint of the
heat pump compared with DHW
setpoint
With fresh air temperature :
Lower than p. 560 the boiler is enabled
Higher than p. 560 + p. 561 the heat pump is enabled
With system water temperature :
Lower than p. 558 the heat pump is disabled
Higher than p. 558 - p. 559 the heat pump is enabled
With fresh air temperature :
Lower than p. 647 the compressors are disabile and is
activated only the heater
Higher than p. 652 only the compressors are enabled
Included between p. 647 and p. 652 resistances and heat
pump are enabled