M0Q940G14-03 WSAT-XIN 21-171 27
7.14 Circulating pump: energy saving mode
Parameter modication Keys Esc + Set Menu dS Menu PI
The function is enabled by default
To deactivate the funcion: PI22 = 0
Heat pump
Off
Pi22
ON
Pi22
pump
ON
Off
Pi03
7.15 Circulating pump: anti-lock function
The function prevents mechanical locks of the circulation pump caused by prolonged inactivity.
Parameter modication Keys Esc + Set Menu dS Menu PI
PI01 max. switch-o time of the circulating pump.
PI03 switch-on time of the circulating pump
The function is enabled by default
To deactivate the funcion: PI01 = 0
Off
Pi01
ON
ON
Off
Pi03
Heat pump
pump