Digital fire detection control panel
COMPACT LYON
6
FIRE PRETECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - cofem@cofem.com - www.cofem.com
1.3.- Characteristics
Base control panel of 1 or 2 loops.
Allows 99 connection elements per loop.
All the loop elements are monitored, except the
KABY loop isolator.
Capacity for up to 64 configurable relays.
Enables programming of 99 zones.
File that stores up to 4095 events with date and time.
Monitored delayable general siren output identified as S1 SIRENA (Sounder).
Voltage-free non-monitored alarm output identified as S1 ALARMA (Alarm).
Monitored delayable general failure output identified as S1 AVERIA (Fault).
Evacuation button.
Backlit LCD display of 4 lines and 40 characters.
Incorporates Spanish, English, French, Italian, Hungarian, Ukrainian and Portuguese).
Configurable and manageable through Easy-Conet PC software.
Allows connection to an external keyboard (PC standard – PS2).
Allows connection of up to 15 repeaters.
It allows the connection of up to 15 control panels in network.
Contact ID (See specific manual of this functionality).
IP30.
Certified according to EN 54-2 and EN 54-4 Standard.
CE marked.
1.4.- Composition of the control panel
Backlit LCD display of 4 lines and 40 characters.
Keyboard made up of 13 keys that form two groups; one where the menu handling keys can be
found and the other where specific control panel functions may be performed.
15 LEDs that enable quick viewing of the control panel status (Supply, Mode of operation, Alarms
and Failures).
Communications port: RS485 and USB 2.0.
Power supply: independent module responsible for controlling the Voltage of the primary 30V
supply that supplies the other boards. There are inside: protection fuses, 30 V output, battery
connection terminals, relay outputs:
S1 SIRENA: Sounder: delayable monitored relay.
S2 ALARMA: Alarm: Voltage-free relay.
S3 AVERÍA: Failure: monitored relay
Multitasking
CPU: within the CPU there are a loop controller, a power controller, two-loop driver,
communication port 485 and USB 2.0 compatible.