EasyManua.ls Logo

Coleman TH4B4221H User Manual

Coleman TH4B4221H
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
TECHNICAL GUIDE
LX
SERIES
SPLIT SYSTEM
HEAT PUMPS
14 SEER – R-410A – 1 PHASE
1.5 THRU 5 NOMINAL TONS
MODELS: TH4B18 THRU 60
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at
www.upgnet.com and www.york.com
Additional rating information can be found at
www.ahridirectory.org
WARRANTY SUMMARY*
Standard 5-year limited parts warranty.
Standard 10-year limited compressor warranty.
Extended 10-Years limited parts warranty when product is
registered online within 90 days of purchase for replacement
or closing for new home construction.
*Does not apply to R-22 models, 3-Phase models, or internet sales.
See Limited Warranty certificate in User's Information Manual for details.
FOR INSTALLATION IN ALL US REGIONS AND CANADA
Installation Allowed
®
5005749-CTG-A-0216
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DESCRIPTION
The TH4 models are the newest offering in our successful LX
Series split system heat pump lineup. These outdoor units are
optimized for the new 14 SEER / 8.2 HSPF Minimum Efficiency
in all US Regions, and are specifically designed to be matched
with Coleman indoor coils, furnaces, and air handlers to provide
a complete system solution.
FEATURES
Easier Installation - Independent panels provide quick
access for unit setup. Installation time is reduced by easy
power and control wiring access. Options are provided for
indoor piston or TXV. The factory installed filter-drier and fac-
tory charge for a 15-Ft lineset means less time spent brazing
and charging the system. The small base dimension and
reduced unit size make for easier retrofits.
Accessible Information - QR code on unit provides quick
access to technical documents and warranty information.
Durable Finish - The coated steel wire fan guard, coated
external fasteners, and pre-treated G90-equivalent galva-
nized steel chassis components resist corrosion and rust
creep. Titanium colored powdercoat paint further protects
external panels.
Rugged Coil Protection - Coils are protected from mechan-
ical damage by a proven stamped steel coil guard design.
Quality Coils - Enhanced aluminum fins are mechanically
bonded to copper tubing.
Protected Compressor - Compressors are protected inter-
nally by a high pressure relief valve and a temperature sen-
sor, and externally by the system high and low pressure
switches. The liquid line filter-drier is factory installed to pro-
tect the compressor against moisture and debris.
Reliable Operation - Ball bearing fan motors provide supe-
rior performance in extreme temperatures. Factory installed
accumulator ensures proper functioning across a wide range
of conditions.
Environmentally Friendly - CFC-free R-410A refrigerant
delivers environmentally friendly performance with zero
ozone depletion.
Top Discharge - Air is blown up, away from the structure
and any landscaping and allows compact location on multi-
unit applications.
Low Operating Sound Levels - Developed using CFD and
FEA tools, the sturdy cabinet and top design provides sound
performance of 75 dBA or lower. Compatible accessories for
further sound reduction are also available.
Better Service Access - Diagonal base valves with open
access for low-loss fittings, single panel access to the electri-
cal controls, full corner access, and removable fan guard
allow easy access for unit maintenance.
Agency Listed - Safety certified by CSA to UL 1995 / CSA
22.2. Performance certified to ANSI/AHRI Standard 210/240
in accordance with the Unitary Small Equipment certification
program.
Question and Answer IconNeed help?

Do you have a question about the Coleman TH4B4221H and is the answer not in the manual?

Coleman TH4B4221H Specifications

General IconGeneral
BrandColeman
ModelTH4B4221H
CategoryHeat Pump
LanguageEnglish

Summary

FEATURES

Easier Installation

Independent panels for quick setup, easy wiring access, factory filter-drier, and charge.

Protected Compressor

Internal protection via relief valve/sensor; external via pressure switches; filter-drier included.

Low Operating Sound Levels

Developed using CFD/FEA; sturdy cabinet provides sound performance of 75 dBA or lower.

Better Service Access

Diagonal base valves, single panel access, full corner access, removable fan guard.

NOMENCLATURE

NOMINAL EFFICIENCY AND STAGING

4 = 14 SEER / 1-Stage (US Southeast or Southwest Region)

PHYSICAL AND ELECTRICAL DATA

SYSTEM CAPACITY - Single Piece and Modular Air Handlers

SYSTEM CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils (Coil Only Ratings)

SYSTEM CAPACITY - With High Efficiency Motor Furnaces

APPLICATION & ACCESSORIES

SOUND POWER RATINGS - HEATING

MECHANICAL SPECIFICATIONS

MANUFACTURE AND CERTIFICATIONS

ISO 9001 certified, CSA certified, ANSI/AHRI certified, sound tested, manufactured in USA.

UNIT APPLICATION

Specifies operating limits for cooling, heating, linesets, wall clearance, and sound.

UNIT ACCESS

Details access points for maintenance: fan guard, electrical compartment, blockoff panel, electrical panel.

TYPICAL INSTALLATION

PERFORMANCE DATA - 1.5 ΤΟΝ

HEATING PERFORMANCE DATA

PERFORMANCE DATA - 2.5 ΤΟΝ

PERFORMANCE DATA - 3.5 ΤΟΝ

PERFORMANCE DATA - 4 ΤΟΝ

PERFORMANCE DATA - 5 ΤΟΝ